When setting parameters, refer to the instruction manual (applied) and understand instructions.
When using motors under General-purpose magnetic flux vector
control, the offline auto tuning can be executed to automatically
calculate the motor constant.
When executing the offline auto tuning under V/F control, set the
motor constant (R1) and the
Pr.298 Frequency search gain
required
for the frequency search at the automatic restart after
instantaneous power failure.
You can copy the offline auto tuning data (motor constants) to
another inverter with the PU (FR-PU07).
Even when motors (other manufacturer's motor, SF-JRC, etc.) other
than Mitsubishi standard motor (SF-JR 0.4kW or higher), high
efficiency motor (SF-HR 0.2kW or higher), and Mitsubishi constant-
torque motor (SF-JRCA 4P, SF-HRCA 0.4kW to 15kW) are used or
the wiring length is long (30m or more as a reference), using the
offline auto tuning function runs the motor with the optimum
operating characteristics.
The offline auto tuning conditions
A motor is connected.
The motor capacity is the same as or one rank lower than the
inverter capacity.
A high-slip motor, high-speed motor and special motor cannot be
tuned.
The maximum frequency is 120Hz.
As the motor may run slightly, fix the motor securely with a
mechanical brake or make sure that there will be no problem in
safety if the motor runs.
Special caution is required in vertical lift applications.
Note that tuning performance is unaffected even if the motor runs
slightly.
(1) Initial settings and specifications for RS-485
communication
(Pr.117 to Pr.124)
Used to perform required settings for RS-485 communication
between the inverter and personal computer.
There are two different communications: communication
using the PU connector of the inverter and communication
using the RS-485 terminals.
You can perform parameter setting, monitor, etc. using the
Mitsubishi inverter protocol or MODBUS RTU protocol.
To make communication between the personal computer
and inverter, initialization of the communication
specifications must be made to the inverter.
Data communication cannot be made if the initial settings
are not made or there is any setting error.
When making communication via the MODBUS RTU protocol (
Pr.549
=
"1"), the setting range is as indicated in parentheses.
82 to 84, 90, 96, 298
Offline auto tuning
Pr.82 Motor excitation current
Pr.83 Rated motor voltage
Pr.84 Rated motor frequency
Pr.90 Motor constant (R1)
Pr.96 Auto tuning setting/status
Pr.298 Frequency search gain
Parameter
Number
Setting
Range
Description
96
0
(initial
value)
Offline auto tuning is not performed.
11
Offline auto tuning for General-purpose
magnetic flux vector control (motor constant
(R1) only)
21
Offline auto tuning for V/F control (automatic
restart after instantaneous power failure (with
frequency search))
V/F
V/F
V/F
GP
MFVC
GP
MFVC
GP
MFVC
117 to 124, 342, 343, 502, 549, 779
Initial communication setting
Pr.117 PU communication station number
Pr.118 PU communication speed
Pr.119 PU communication stop bit length
Pr.120 PU communication parity check
Pr.121 Number of PU communication retries
Pr.122 PU communication check time interval
Pr.123 PU communication waiting time setting
Pr.124 PU communication CR/LF selection
Pr.342 Communication EEPROM write selection
Pr.343 Communication error count
Pr.502 Stop mode selection at communication error
Pr.549 Protocol selection
Pr.779 Operation frequency during communication error
Pr.
Number
Setting Range
Description
117
0 to 31
(0 to 247)
Specify the inverter station number.
Set the inverter station numbers when
two or more inverters are connected to
one personal computer
118
48, 96, 192, 384
Set the communication speed.
The setting value
100 equals the
communication speed.
For example, the communication speed is
19200bps when the setting value is "192".
119
Stop bit length
Data length
0
1 bit
8 bits
1 (initial value)
2 bits
10
1 bit
7 bits
11
2 bits
120
0
Without parity check
1
With odd parity check
2 (initial value)
With even parity check
121
0 to 10
Set the permissible number of retries at
occurrence of a data receive error. If the
number of consecutive errors exceeds
the permissible value, the inverter will
come to trip.
9999
If a communication error occurs, the
inverter will not come to trip.
122
0 (initial value)
RS-485 communication can be made.
Note that a communication fault (E.PUE)
occurs as soon as the inverter is
switched to the operation mode with
command source. (NET operation mode
at initial value)
0.1 to 999.8s
Set the interval of communication check
time.
If a no-communication state persists for
longer than the permissible time, the
inverter will come to trip.
9999
No communication check
123
0 to 150ms
Set the waiting time between data
transmission to the inverter and
response.
9999 (initial value)
Set with communication data.
124
0
Without CR/LF
1 (initial value)
With CR
2
With CR/LF