DC reactor (for power
supply coordination)
FR-HEL-(H)
K
Improves the power factor and reduces the harmonic current at the input side. Connect a DC reactor in the DC section of the inverter.
Selection method
Select a DC reactor according to the applied motor capacity. (When a general-purpose motor is used, select it according to the motor capacity even if
the capacity is smaller than the inverter capacity.)
Connection diagram
Connect a DC reactor to the inverter terminals P1 and P. Before connecting, make sure to remove the jumper across the terminals P1 and P.
(If the jumper is left attached, no power factor improvement can be obtained.)
The connection cable between the reactor and the inverter should be as short as possible (5m or less).
Outline dimension
EMC Directive
compliant noise filter
SF
FR-E5NF-H
K
(400V class)
A noise filter that complies with the European EMC Directive (EN61800-3 2nd Environment Category C3).
Radio noise filter
FR-BIF (200V class)
FR-BIF-H (400V class)
Outline dimension
(Note) 1. The radio noise filter cannot be connected to the inverter output side.
2. Keep the wiring as short as possible and connect it to the inverter terminal block.
3. The radio noise filter cannot be connected when a Filterpack is connected.
Name (model)
Specification and Structure
Three-phase
AC power supply
R/L1
S/L2
T/L3
Motor
U
V
W
P1
P1
P
M
P/+
N/-
FR-HEL
Inverter
Remove a jumper
across terminals P1-P.
The connection cable should be
5m maximum.
(Unit mm)
(Note) 1. The size of the cables used should be equal to or larger than that of the power supply cables (R/L1,
S/L2, T/ L3).
(Refer to page 68.)
2. Approximately 93% of the power factor improving effect can be obtained (94.4% when calculated
with 1 power factor for the fundamental wave according to the Architectural Standard
Specifications (Electrical Installation) (2013 revision) supervised by the Ministry of Land,
Infrastructure, Transport and Tourism of Japan).
3. This is a sample outline dimension drawing. The shape differs by the model.
W1 and D1 indicate distances between installation holes. The installation hole size is indicated by d.
4. Install DC reactors (FR-HEL) on a horizontal or vertical surface.
5. Keep enough clearance around the reactor because it heats up.
(Keep a clearance of minimum 10cm each on top and bottom and minimum 5cm each on right
and left regardless of the installation orientation.)
Model
W W1 H
D
D1 d
Mass
(kg)
Model
W W1 H
D
D1 d
Mass
(kg)
200V
0.4K
70
60
71
61
M4 0.4
400V
H0.4K
90
75
78
60
M5 0.6
0.75K
85
74
81
61
M4 0.5
H0.75K
66
50 100
70
48 M4 0.8
1.5K
85
74
81
70
M4 0.8
H1.5K
66
50 100
80
54 M4
1
2.2K
85
74
81
70
M4 0.9
H2.2K
76
50
110
80
54 M4 1.3
3.7K
77
55
92
82
57 M4 1.5
H3.7K
86
55 120
95
69 M4 2.3
5.5K
77
55
92
92
67 M4 1.9
H5.5K
96
60 128 100 75 M5
3
7.5K
86
60
113
98
72 M4 2.5
H7.5K
96
60 128 105 80 M5 3.5
11K
105 64 133 112
79 M6 3.3
H11K
105 75 137 110
85 M5 4.5
15K
105 64 133 115
84 M6 4.1
H15K
105 75 152 125 95 M5
5
Less than D
W
W1
H
FR-HEL-0.4K to 2.2K
FR-HEL-H0.4K
W
Less than D
FR-HEL-3.7K to 15K
FR-HEL-H0.75K to H15K
W1
D1
H
The depth required for installation will increase by 12mm when the intercompatibility attachment is installed.
The indicated leakage current is equivalent to one phase of the three-phase three-wire Y-connection power
supply. For the three-phase three-wire
-connection power supply, the value becomes approximately three
times larger than the listed value.
(Note) This is a sample outline dimension drawing. The shape differs by the model.
Countermeasures for leakage current
Take following measures to prevent a malfunction of peripheral device or an electric shock accident due to leakage
current.
1) Ground (earth) the noise filter before connecting the power supply. Check that the noise filter is grounded
(earthed) securely through the enclosure.
2) Select an earth leakage circuit breaker or earth leakage relay to allow for the leakage current of noise filter. An earth
leakage circuit breaker may not be used when the leakage current of noise filter is too large. Use an earth leakage relay with a large rated sensitivity
current. If an earth leakage circuit breaker or earth leakage relay cannot be used, securely perform grounding (earthing) as directed in (1).
Noise filter model Applicable Inverter Model
Intercompat-
ibility
attachment
Outline Dimension
(Unit: mm)
Mass
(kg)
Leakage
current (mA)
(Reference
value)
Loss
(W)
W
H
D
SF1306
FR-F720PJ-0.4K to 1.5K
110
200
36.5
0.7
10
7.3
SF1309
FR-F720PJ-2.2K, 3.7K
FR-E5T
200
282
57
2.1
15
15
FR-E5NF-H0.75K
FR-F740PJ-0.4K, 0.75K
140
210
46
1.1
22.6
5.5
FR-E5NF-H3.7K
FR-F740PJ-1.5K to 3.7K
140
210
46
1.2
44.5
8
FR-E5NF-H7.5K
FR-F740PJ-5.5K, 7.5K
220
210
47
2
68.4
15
Noise filter model Applicable Inverter Model
Intercompat-
ibility
attachment
Outline Dimension
(Unit: mm)
Mass
(kg)
Leakage
current (mA)
(Reference
value)
Loss
(W)
W
H
D
D1
SF1260
FR-F720PJ-5.5K to 11K
FR-A5AT03
222 468
80
39
5
440
118
SF1261
FR-F720PJ-15K
FR-AAT02
253 600
86
38
9.3
71
37
SF1175
FR-F740PJ-11K, 15K
FR-AAT02
253 530
60
35
4.7
76
56
W
H
D
W
H
D
D1
Red White Blue
300
29
58
41
29
7
44
4
φ
4.3 hole
R S T
Green
Leakage current
: 4mA
(Unit: mm)
Earth (ground)
Radio noise filter
FR-BIF(-H)
T/L3
S/L2
R/L1
Inverter
MCCB
Power
supply