Features
Options
Precautions
Motor
Connection
example
Standard
specs.
Outline
dimensions
Parameter
list
Parameter
descriptions
Protective
functions
IPM motor
control
Compatibility
W
arranty
Te
rminal connection
diagrams
T
e
rminal specs.
Operation panel
Parameter unit
FR Configurator
81
Initialization can be performed by setting
Pr.998 IPM parameter initialization
or by choosing the mode on the operation panel.
By selecting IPM motor control from the parameter setting mode or with
Pr.998 IPM parameter initialization
, the parameter
settings in the following table change to the settings required to drive an IPM motor. The changed settings differ according to
the IPM motor specification (capacity). Refer to the IPM motor specification list shown below.
Performing parameter clear or all parameter clear sets back the parameter settings to the settings required to drive a general-
purpose motor.
Pr.998
Setting
Description
Operation after selecting the parameter
setting mode on the operation panel
0
Parameter settings for a general-purpose motor (frequency)
"IPM"
Write "0"
1
Parameter settings for a high-efficiency IPM motor MM-EF (rotations per
minute)
"IPM"
Write "1"
12
Parameter settings for a premium high-efficiency IPM motor MM-EFS
(rotations per minute)
"IPM"
Write "12"
101
Parameter settings for a high-efficiency IPM motor MM-EF (frequency)
Invalid
112
Parameter settings for a premium high-efficiency IPM motor MM-EFS
(frequency)
Invalid
IPM parameter initialization list
Parameter
Name
Setting
Setting increments
General-purpose
motor
IPM motor
(rotations per
minute)
IPM motor
(frequency)
Pr.998
0
(Initial setting)
1 (MM-EF),
12 (MM-EFS)
101 (MM-EF),
112 (MM-EFS)
1, 12
0, 101, 112
1
Maximum frequency
120Hz
Maximum motor
rotations per minute
Maximum motor
frequency
1 r/min
0.01Hz
4
Multi-speed setting (high speed)
60Hz
Rated motor
rotations per minute
Rated motor
frequency
1 r/min
0.01Hz
9
Electronic thermal O/L relay
Rated inverter current
Rated motor current
0.01A
13
Starting frequency
0.5Hz
Minimum rotations
per minute
Minimum
frequency
1 r/min
0.01Hz
15
Jog frequency
5Hz
Minimum rotations
per minute
Minimum frequency
1 r/min
0.01Hz
18
High speed maximum frequency
120Hz
Maximum motor
rotations per minute
Maximum motor
frequency
1 r/min
0.01Hz
20
Acceleration/deceleration
reference frequency
60Hz
Rated motor
rotations per minute
Rated motor
frequency
1 r/min
0.01Hz
22
Stall prevention operation level
120%
120% (Short-time motor torque)
0.1%
37
Speed display
0
0
1
55
Frequency monitoring reference
60Hz
Rated motor
rotations per minute
Rated motor
frequency
1 r/min
0.01Hz
56
Current monitoring reference
Rated inverter current
Rated motor current
0.01A
71
Applied motor
0
Pr.998
= 1,101 : 120
Pr.998
= 12,112 : 210
1
80
Motor capacity
9999
Inverter capacity
0.01kW
125(903)
Terminal 2 frequency setting gain
frequency
60Hz
Rated motor
rotations per minute
Rated motor
frequency
1 r/min
0.01Hz
126(905)
Terminal 4 frequency setting gain
frequency
60Hz
Rated motor
rotations per minute
Rated motor
frequency
1 r/min
0.01Hz
144
Speed setting switchover
4
106 (Number of motor
poles + 100)
6 (Number of motor
poles)
1
240
Soft-PWM operation selection
1
0
1
260
PWM frequency automatic
switchover
1
1
1
374
Overspeed detection level
9999
Maximum motor
rotations per minute
105%
Maximum motor
frequency
105%
1 r/min
0.01Hz
505
Speed setting reference
60Hz
Rated motor frequency
0.01Hz
557
Current average value monitor signal
output reference current
Rated inverter current
Rated motor current
0.01A
870
Speed detection hysteresis
0Hz
10 r/min
(Speed detection
hysteresis rotations
per minute)
0.5Hz
(Speed detection
hysteresis
frequency)
1 r/min
0.01Hz
885
Regeneration avoidance
compensation frequency limit value
6Hz
Minimum rotations
per minute
Minimum frequency
1 r/min
0.01Hz
Содержание F720PJ-11KF
Страница 88: ...88 MEMO ...