When setting parameters, refer to the instruction manual (applied) and understand instructions.
The monitor to be displayed on the main screen of the operation
panel and parameter unit (FR-PU07) can be selected.
Selected by the parameter unit (FR-PU07)
The cumulative energization time and actual operation time are
accumulated from 0 to 65535 hours, then cleared, and accumulated
again from 0.
When the operation panel is used, up to 65.53 (65530h) is displayed as
1h=0.001 and then accumulated from 0.
The actual operation time is not added up if the cumulative operation
time before power supply-off is less than 1h.
When using the parameter unit (FR-PU07), “kW” is displayed.
Since the panel display of the operation panel is 4 digits in length, the
monitor value of more than "9999" is displayed as "----".
The cumulative power monitor value digit can be shifted to the right
by the number set in
Pr. 891
.
By setting “0” in
Pr. 170
, the cumulative power monitor can be
cleared.
You can check the numbers of cumulative energization time monitor
exceeded 65535h with
Pr. 563
and the numbers of actual operation
time monitor exceeded 65535h with
Pr. 564
.
Writing "0" in
Pr. 171
clears the actual operation time monitor.
When
Pr. 52
is set to "100", the set frequency monitor is displayed
during a stop and the output frequency monitor is displayed during
operation. (LED of Hz flickers during stop and is lit during operation.)
The set frequency displayed indicates the frequency to be output when
the start command is ON. Different from the frequency setting displayed
when
Pr. 52
= "5", the value based on maximum/minimum frequency and
frequency jump is displayed.
Set the full scale value when monitoring the output from terminal FM.
For the applicable monitor names, refer to the description on
Pr.52
.
52, 54, 170, 171, 268, 563, 564, 891
DU/PU monitor change, cumulative
monitor clear
Pr.52 DU/PU main display data selection
Pr.54 FM terminal function selection
Pr.170 Watt-hour meter clear
Pr.171 Operation hour meter clear
Pr.268 Monitor decimal digits selection
Pr.563 Energization time carrying-over times
Pr.564 Operating time carrying-over times
Pr.891 Cumulative power monitor digit shifted times
Types of
Monitor
Increments
Pr.52
setting
Pr.54
(FM)
setting
Full Scale
Value
operation
panel
LED
PU main
monitor
Output
frequency
0.01Hz
0/100
1
Pr.55
Output current
0.01A
0/100
2
Pr.56
Output voltage
0.1V
0/100
3
200V class: 400V
400V class: 800V
Alarm display
0/100
Frequency
setting
0.01Hz
5
5
Pr.55
Converter
output voltage
0.1V
8
8
200V class: 400V
400V class: 800V
Regenerative
brake duty
0.1%
9
9
Brake duty set in
Pr. 30
and
Pr. 70
Electronic
thermal relay
function load
factor
0.1%
10
10
Electronic
thermal relay
function
operation level
Output current
peak value
0.01A
11
11
Pr.56
Converter
output voltage
peak value
0.1V
12
12
200V class: 400V
400V class: 800V
Output power
0.01kW
14
14
Rated inverter
power
2
Input terminal
status
Output terminal
status
Cumulative
energization
1h
20
Reference
voltage output
21
Actual operation
time
1h
23
Motor load
factor
0.1%
24
24
200%
Cumulative
power
0.01kWh
25
Power saving
effect
Variable
according
to
parameters
50
50
Inverter capacity
Cumulative
saving power
51
PID set point
0.1%
52
52
100%
PID measured
value
0.1%
53
53
100%
PID deviation
value
0.1%
54
Inverter I/O
terminal
monitor
55
Motor thermal
load factor
0.1%
61
61
Thermal relay
operation level
(100%)
Inverter thermal
load factor
0.1%
62
62
Thermal relay
operation level
(100%)
PTC thermistor
resistance
0.01k
64
Pr.268
setting
Description
9999
(initial value)
No function
0
When 1 or 2 decimal places (0.1 increments or 0.01
increments) are monitored, the decimal places are
dropped and the monitor displays an integer value (1
increments).
The monitor value of 0.99 or less is displayed as 0.
1
When 2 decimal places (0.01 increments) are
monitored, the 0.01 decimal place is dropped and the
monitor displays the first decimal place (0.1
increments).
When the monitor display digit is originally in 1
increments, it is displayed unchanged in 1
increments.
Pr.52
0
100
During
operation/stop
During stop
During
running
Output
frequency
Output frequency
Set frequency
Output
frequency
Output
current
Output current
Output
voltage
Output voltage
Fault
display
Alarm display
55, 56
Terminal FM output monitor change
Pr.55 Frequency monitoring reference
Pr.56 Current monitoring reference
Monitor
Reference parameter
Initial Value
Frequency
Pr.55
60Hz
Current
Pr.56
Rated inverter current
500A
2400
pulse/s
1440
pulse/s
Output frequency
reference
Output current
reference
400Hz
Pr.56
Pulse speed(terminal FM)
Pr.55