–166–
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
4210
4220
Breaking of
overcurrent
(Variable
capacity unit)
Bus voltage
abnormality
(Variable
capacity unit)
1
If IDC 103 A peak is de-
tected during inverter opera-
tion.
2
If the voltage of the INV
board’s sensor circuit input is
what it should not normally be.
1
If VDC
400 V is detected
during inverter operation.
2
If VDC
800 V is detected
during inverter operation.
•
Check if an instantaneous power
failure or power failure, etc. has
occurred.
•
Check if the voltage is the rated
voltage value.
Check 1, the connections, 2, contact
at the connectors, 3 tightening torque
at screw tightened portions, 4, wiring
polarities, 5, for broken wires, and 6,
for grounding in the following wiring.
TB1A ~ DS ~ [52C, R1, R5] ~ [C2,
C3] ~ TRM Wiring
TRM ~ CNVDC Wiring
TRM ~ Compressor Wiring
[CN2-1, CN2-2, CN2-3, CN3]
~ TRM Wiring
*
Check if the wiring polarities are as
shown on the wiring diagram plate.
*
Check the coil resistances and in-
sulation resistance of the compres-
sor.
Go to “Treatment of Inverter/Compres-
sor Related Trouble.”
•
Check if an instantaneous stop or
power failure, etc. has occurred.
•
Check if the voltage is the rated
voltage value.
Check 1, the connections, 2, contact
at the connectors, 3 tightening torque
at screw tightened portions, 4, wiring
polarities, 5, for broken wires, and 6,
for grounding in the following wiring.
TB1A ~ DS ~ [52C, R1, R5] ~ [C2, C3]
~ TRM Wiring
TRM ~ CNVDC Wiring
*
Check if the wiring polarities are as
shown on the wiring diagram plate.
To judge failure of R1 and R5, go to
“Individual Parts Failure Judgment
Methods.”
To judge failure of the 52C, go to “Indi-
vidual Parts Failure Judgment Meth-
ods.”
To judge failure of the DS, go to “Indi-
vidual Parts Failure Judgment Meth-
ods.”
To judge failure of the DCL, go to “In-
dividual Parts Failure Judgment Meth-
ods.”
•
Check the wiring between the TRM
and the compressor.
•
Check the compressor’s insulation
resistance.
If none of the items in 1) to 7) is appli-
cable, and if the trouble reappears
even after the power is switched on
again, replace the INV board (when
replacing the circuit board, be sure to
connect all the connectors, ground
wires, etc. securely).
1) The power supply voltage is abnor-
mal.
2) The wiring is defective.
3) The inverter/compressor is defective.
1) The power supply voltage is abnor-
mal.
2) The wiring is defective.
3) The rush current prevention resistors
(R1, 5) are defective.
4) The electromagnetic contactor (52C)
is defective.
5) The diode stack (DS) is defective.
6) The reactor (DCL) is defective.
7) The inverter output is grounded.
8) The circuit board is defective.
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...