–178–
If different units within one system are using different types of refrigerant as shown in table 1 below, the system will not
operate correctly.
Table1
Refrigerant type
Example 1
Example 2
Example 3
R407C
R407C
R22
R407C
R22
R407C
R22 only
–
–
Check that the address of Outdoor unit is being set
to 51 ~ 100.
Reset the address if it stays out of the range, while
shutting the power source off.
a) Check that the power has not been cut-off due
to the power supply of transmission booster
being connected to the indoor unit switch.
(The air conditioner will not operate correctly if
the power supply of transmission booster is
not turned on.)
→
Reset the outdoor unit power supply.
a) Replace the old remote controller by the new
remote controller.
Use the same type of refrigerant in all units
included in the system.
Address setting error
• Erroneous setting of Outdoor
unit address
Error source: Outdoor unit
The indoor unit will not operate
because it is not correctly con-
nected to the outdoor unit of the
same refrigerant system.
Remote control sensor error
Error not providing the tempera-
ture designed to remote control-
ler sensor.
Error source: Indoor unit
Different Refrigerant unit
connected error
1) Setting error of Outdoor unit address
The address of Outdoor unit is not
being set to 51~100.
1) The transmission booster is defec-
tive, has disconnected wires, or the
power has been cut-off.
2) The transmission booster and out-
door unit power supplies have been
cut-off.
1) In case when the old type remote
controller for M-NET is used and the
remote controller sensor is designed
on indoor unit. (SW1-1 turned ON)
(See Table 1)
Checking
code
7105
7110
7111
7130
Meaning, detecting method
Cause
Checking method & Countermeasure
Variable capacity unit
Constant capacity unit
Indoor units
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...