–78–
2
Switching No. 3 compressor from operation to stopping
When the required performance is exceeded with the No. 1 and No. 2 variable capacity unit compressors and the
constant capacity unit No. 3 compressor in operation, the No. 3 compressor will be stopped.
3) Pressure control
• The upper limit value for the high pressure (Pd) has been set for each frequency. When this value is exceeded, the
frequency is reduced every 30 seconds.
• While the constant capacity unit is in operation, if the high pressure (63HS) value exceeds 26 kg/cm
2
G (2.55 MPa),
the constant capacity unit compressor will be stopped.
4) Discharge temperature control
1
The discharge temperature of the compressor (Variable capacity unit: TH11, TH12, Constant capacity unit:
TH11) is monitored during the operation. If the upper limit is exceeded, the frequency is reduced by 5 Hz.
• Control is performed every 30 seconds after 30 seconds at the compressor starting.
• The operating temperature is 124
°
C (No.1 compressor) or 115
°
C (No. 2, 3 compressor).
2
While the constant capacity unit is in operation, if the constant capacity unit discharge temperature (TH11)
exceeds 115
°
C, the constant capacity unit compressor will be stopped.
5) Compressor frequency control
1
Ordinary control
The ordinary control is performed after the following times have passed.
• 30 seconds after the start of the compressor or 30 seconds after the completion of defrosting.
• 30 seconds after frequency control operation by the discharge temperature or the high pressure.
2
Amount of frequency fluctuation
The amount of frequency fluctuation is controlled in response to the evaporation temperature (Te) and the
condensation temperature (Tc) so that it will be approached the target values.
3
Frequency control back-up by the bypass valve
Frequency control is backed-up by the turning on (opening) the bypass valve (SV4) when only the No. 1 com-
pressor is operated at its lowest frequency.
• Cooling
After the compressor has been operated for 15 minutes and only the No. 1 compressor is operated in un-load
(its lowest frequency), the bypass valve is turned ON when the low pressure (63LS) is 1.0 kg/cm
2
G (0.098 MPa)
or less and turned OFF when it is 2.0 kg/cm
2
G (0.196 MPa) or more.
• Heating
After the compressor has been operated for 3 minutes and only the No. 1 compressor is operated in un-load (its
lowest frequency), the bypass valve is turned ON when the high pressure (Pd) exceeds 27 kg/cm
2
(2.65 MPa)
and turned OFF when it is 24 kg/cm
2
(2.35 MPa) or less.
ON
OFF
1.0 kg/cm
2
G
(0.098 MPa)
2.0 kg/cm
2
G
(0.196 MPa)
24 kg/cm
2
G
ON
OFF
27 kg/cm
2
G
(2.35 MPa)
(2.65 MPa)
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...