Additional Refrigerant Charge Volume
At the time of shipping from the factory, the outdoor unit is charged with the amount of refrigerant shown in the
following table, but since no extension piping is included, please carry out additional charging on-site.
Variable Capacity Unit
Constant Capacity Unit
Outdoor Unit Model
PUHY-(P)400YMF-B PUHY-(P)500YMF-B PUHN-(P)200YMF-B
PUHN-(P)250YMF-B
Refrigerant Charge Volume
16 kg
22 kg
6.5 kg
8.5 kg
Calculation Formula
Calculate the additional refrigerant volume by calculating the size of the extension liquid piping and its length (units: m).
Additional Refrigerant Volume
(kg) = (0.29
×
L
1
) + (0.25
×
L
2
) + (0.12
×
L
3
) + (0.06
×
L
4
) + (0.024
×
L
5
) +
α
In the calculation results, round up fractions smaller than 0.01 kg. (Example: 18.54 kg
→
18.6 kg)
L
1
: Length of
ø
19.05 liquid pipe (m)
L
2
: Length of
ø
15.88 liquid pipe (m)
L
3
: Length of
ø
12.7 liquid pipe (m)
L
4
: Length of
ø
9.52 liquid pipe (m)
L
5
: Length of
ø
6.35 liquid pipe (m)
α
: refer to the calculation table.
Example PUHY-P600YSMF-B
(
α
Calculation Table)
Total Capacity of Connected Indoor Units
α
161 ~ 330
2.0 kg
331 ~ 480
2.5 kg
481 ~ 630
3.0 kg
631 ~
4.0 kg
ø
12.7
(3 m)
ø
15.88
(1 m)
ø
19.05
(30 m)
ø
15.88
(10 m)
ø
12.7 (20 m)
ø
12.7 (10 m)
ø
12.7
(10 m)
ø
9.52
(10 m)
ø
9.52
(10 m)
ø
6.35
(10 m)
ø
9.52
(20 m)
ø
9.52
(10 m)
ø
9.52
(10 m)
ø
9.52
(10 m)
Each distribution pipe carries liquid.
ø
19.05: 30 m
= 30 m
ø
15.88: 1 m + 10 m
= 11 m
ø
12.7 : 3 m + 10 m + 20 m + 10 m
= 43 m
ø
9.52 : 10 m + 10 m + 20 m + 10 m + 10 m + 10 m = 70 m
ø
6.35 : 10 m
= 10 m
From the formula above we find that:
Add. Refrigerant volume = (0.29
×
30) + (0.25
×
11) + (0.12
×
43) + (0.06
×
70) + (0.024
×
10) + 3 = 24.05 kg
The result of this calculation is 24.05 kg, however we will round to the nearest 0.1 kg:
Add. Refrigerant volume = 24.1 kg.
The total refrigerant level (including the outdoor unit refrigerant charge and the additional volume in the extension pipes)
is over 73 kg, please make the total refrigerant amount = 73 kg.
Original refrigerant amount in the outdoor unit + additional refrigerant amount 73 kg
Example for PUHY-P600YSMF-B
PUHY-P400YMF-B
PUHN-P200YMF-B
Additional refrigerant volume
16 kg
+
6.5 kg
+
51 kg
= 73.5 kg
→
Fix to 73 kg
(Set the additional refrigerant volume to 50.5 kg.)
Model
80
Model
125
Model
32
Model
125
Model
80
Model
63
Model
71
Caution: (R407C)
When charging with refrigerant, be sure to charge from the liquid side. If charging from the gas side, it will cause
the refrigerant composition to change inside the unit and the composition of the refrigerant remaining in the
canister will also change.
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...