–120–
(2)
Refrigerant Volume
1) Checking the Operating Condition
Operate all the indoor units on cooling or on heating, checking the discharge temperature, sub-cooling, low pressure
saturation temperature, inlet temperature, shell bottom temperature, fluid level, fluid step, etc. and rendering an overall
judgment.
Note:
Depending on the operating state, AL = 0 has the meaning does not mean that there is insufficient refrigerant.
2) Cautions When Judging the Liquid Level
If you are judging the liquid level, be sure to use it only after making sure the liquid level sensor function (sensor and
heater) is operating normally.
3) Check the refrigerant volume by LED monitor display using the LED.
Set the LED monitor display switch (SW1) as shown below and check the past information (history) concerning the
refrigerant volume.
Set SW1 as shown in he figure at right.
If LD3 lights up, it indicates the refrigerant charge abnormal delay state just before emergency stop due to refriger-
ant overcharge (1500).
Judgment
Refrigerant volume tends toward
insufficient.
Refrigerant volume tends toward
overcharge.
Check Items
Judgment
1 2 3 4 5 6 7 8 9 10
ON
Condition
1
Discharge temperature is high. (125
°
C or higher)
2
Low pressure saturation temperature is extremely low.
3
Inlet superheating is high (if normal, SH = 20 deg. or lower).
4
Shell bottom temperature is high (the difference with the low pressure saturation
temperature is 70 deg. or greater)
5
Shell temperature is low (the difference with the low pressure saturation temperature is
10 deg. or lower).
6
Liquid level AL = 2
Normal if the resistance is 2.8 k
Ω
±
7 %.
Normal if AC 198 ~ 264 V is output
together with the LED lighting.
1
Liquid Heater Disconnection Check
2
Liquid Heater Output Check
Turn 1 ON on the LED monitor display switch (SW1)
1 2 3 4 5 6 7 8 9 10
ON
, and output
the signal for the heater relay to LED 5, then check the voltage of the heater terminal (AC
198 ~ 264 V) (leave the heater connections as they are).
3
Use the LED monitor display to check if there is misalignment between the actual
temperature and the detected temperature of TH2 ~ TH4.
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...