–176–
Checking
code
6607
(continued)
Meaning, detecting method
No ACK error
When no ACK signal is detected in 6 continuous times with 30 second interval by transmission side
controller, the transmission side detects error.
Note) The address/attribute shown on remote controller indicates the controller not providing
the answer (ACK).
Checking method & countermeasure
System
compo-
sition
Generating
unit address
Display of
trouble
Detecting
method
Cause
(3) Connecting system with system controller (MELANS)
4
System
control-
ler (SC)
Address
which
should not
be existed
Remote
controller
(RC)
–
No reply
(ACK) at
transmission
of IC to SC
–
Trouble of partial remote controller:
1) Faulty wiring of RC transmission line.
2) Slipping off or poor contact of RC transmis-
sion connector.
3) Faulty RC.
4) The transmission booster is defective, has
disconnected wires, or the power has been
cut-off.
Trouble of all IC in one refrigerant system.
1) Error detected by OC unit
Total capacity error
(7100)
Capacity code setting error
(7101)
Connecting number error
(7102)
Address setting error
(7105)
2) Slipping off or short circuit of transmission
line of OC unit terminal block for central con-
trol (TB7).
3) Power source shut down of OC unit.
4) Trouble of OC unit electrical system.
5) The transmission booster is defective, has
disconnected wires, or the power has been
cut-off.
Trouble of all RC:
1) As same that for single refrigerant system.
2) Inserting supply power connector (CN40) to
OC transmission line for centralized control.
3) The transmission booster is defective, has
disconnected wires, or the power has been
cut-off.
4) Faulty MELANS.
1) IC unit is keeping the memory of the original
group setting with RC although the RC ad-
dress was changed later.
The same symptom will appear for the re-
gistration with SC.
2) IC unit is keeping the memory of the original
interlocking registration with Fresh Master with
RC although the Fresh Master address was
changed later.
Check 1) ~ 4) left.
Confirm OC trouble diagnosis LED
→
At trouble generation, check for the
content according to check code.
Check the content of 2) ~ 5) shown left.
Check the causes 1) ~ 4) left.
As some IC units are keeping the me-
mory of the address not existing, de-
lete the information.
Employ one of the deleting method
among two below.
1) Deletion by remote controller.
Delete unnecessary information by
the manual setting function of re-
mote controller.
2) Deletion by connecting information
deleting switch of OC unit.
Be careful that the use of this
method will delete all the group
information set with RC and all
the interlocking information of
Fresh Master and IC unit.
1
Shut down OC unit power
source, and wait for 5 minutes.
2
Turn on the dip switch SW2-2
provided on OC unit control cir-
cuit board.
3
Make OC unit power source, and
wait for 5 minutes.
4
Shut down OC unit power
source, and wait for 5 minutes.
5
Turn off the dip switch SW2-2
provided on OC unit control cir-
cuit board.
6
Make OC unit power source.
No relation with system
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...