–41–
-
Centralized control not
connected.
Storing of refrigeration
system connection
information.
Store IC•OC error history.
Ordinary control
-
-
Ordinary control
-
-
Valid during normal
operation
SW3-2 Function Invalid
Stop all indoor units.
0
°
C
7
°
C
Ordinary control
Ordinary control
-
-
Model 400
-
Display variable capacity
unit operations.
-
-
2-phase modulation
Y Setting
-
-
-
-
When Off
When On
When Off
When On
SWU 1 ~ 2
SW1
1 ~ 8
Refer to LED monitor display on the outdoor board.
9 ~ 10
SW2
1
2
3
4
5
6
7
8
9
10
SW3
1
2
3
4
5
6
7
8
9
10
SW4
1
2
3
4
5
6
7
8
9
10
-
Centralized control
connected.
Deletion of refrigeration
system connection
information.
Erase IC•OC error history.
• Refrigerant volume
adjustment operation.
• Ignore liquid level errors
-
-
Start forced defrosting.
-
-
note: 3
SW3-2 Function Valid
All indoor units test run
ON.
– 2
°
C
12
°
C
Evaporation temperature /
2
°
C lower than normal
-
High pressure / 1.5 ~ 2.5 K
higher than normal
-
-
Model 500
-
Display constant capacity
unit operations.
-
-
3-phase modulation
Super Y Setting
-
-
-
-
Unit Address Setting
For self diagnosis/
operation monitoring
-
Centralized Control
Switch
Deletion of connection
information.
Deletion of error history.
• Adjustment of Refriger-
ant Volume
• Ignore liquid level errors
-
-
Forced defrosting
-
-
Preserve suction pressure
SW3-2 Function Valid/
Invalid
Indoor Unit Test Operation
Defrosting start tempera-
ture .
Defrosting end tempera-
ture.
Target low-pressure
change
-
Target high-pressure
change
-
-
Models
-
Change service LED
-
-
Inverter control
Switch Models
-
-
-
-
Switch
Function
During normal
operation when
power is on.
Invalid 2 hours
after compressor
starts.
PUHY-600·650·700·750 YSMF-B.
PUHY-400·500YMF-B.
1
Variable capacity unit
MAIN board
Function According to Switch Operation
Switch Set Timing
Before power is turned on.
-
Before power is turned on.
Before power is turned on.
During normal operation when
power is on.
-
-
-
-
During normal operation when
power is on.
During normal operation when
power is on.
When SW3-1 is ON after power is
turned on.
During normal operation when
power is on.
During normal operation when
power is on. (Except during
defrosting)
During normal operation when
power is on.
-
During normal operation when
power is on.
-
-
When switching on the power.
-
During normal operation when
power is on.
When SW4-1 is ON
-
When switching on the power.
Before power is turned on.
-
-
-
-
During normal
operation when
power is on.
10 minutes or
more after
compressor
starts.
Set on 51 ~ 100 with the rotary switch.*2
Note 1: Factory setting is SWU 1 to 2 = 00, SW3 - 10 = set by model. All other switches are set to OFF.
Note 2: If the address is set from 01 to 50, it automatically becomes 100.
Note 3: The operation cumulative time of compressor is effective to it only within 1 hour.
Note 4: Factory settings are SW4-6 = OFF, setting = Y.
When operating in Super Y mode, turn SW4-6 ON.
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...