
–179–
[3] LED Monitor Display
(1)
How to read LED for service monitor
By setting of DIP SW1-1 ~ 1-8 and SW4-2, the unit operating condition can be observed with the service LED on the
MAIN board on Variable capacity unit. (For the relation of each DIP SW to the content, see the table provided. Constant
capacity unit operation can also be checked if SW4-2 = ON.)
As shown in the figure below, the LED consist of 7 segments is put in 4 sets side by side for numerical and graphic
display.
OC: Outdoor unit
SV
: Solenoid valve
THHS : Inverter radiator panel
IC : Indoor unit
LEV
: Electronic expansion valve
COMP : Compressor
SW1: Variable capacity unit Main board
E
: Memory storage for service activities (sampling per minute)
7 seg LED
The numerical display includes that of pressure, temperature or the like, while the graphic display includes that of
operating condition, solenoid valve ON/OFF state or the like.
• Numerical display
Example: Display at 18.8 kg/cm
2
G (1.84 MPa) of pressure sensor data (Item No. 56)
• Graphic display (Two LEDs aligned vertically express a flag.)
Example: At forcible powering in outdoor unit operation display
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...