–171–
Checking
code
6602
6603
Meaning, detecting method
Cause
Checking method & Countermeasure
Transmission processor hard-
ware error
Transmission circuit bus-busy
error
1
Collision of data transmission:
Transmission can not be per-
formed for 4 ~ 10 consecutive
minutes due to collision of data
transmission.
2
Data can not be transmitted on
transmission line due to noise
for 4 ~ 10 consecutive minutes.
Note)
The address/attribute
shown on remote
controller indicates the
controller which has
detected error.
Checking method and processing
1) As the voltage of short frequency like
noise is mixed in transmission line
continuously, transmission processor
can not transmit.
2) Faulty controller of generating unit.
a) Check transmission wave shape/noise on trans-
mission line by following <Investigation method
of transmission wave shape/noise>.
→
No noise indicates faulty controller of generat-
ing unit.
→
Noise if existed, check the noise.
CN40 inserted?
Transmission line
installed while turning
power source on?
Check power source of indoor
unit
220 V ~ 240 V?
Check transmission line
work and shield finish
Ground fault or shield
contacted with transmission
line?
System composition?
Single refrigerant
system
Investigation of trans-
mission line noise
Noise exist?
Faulty controller of
generating unit
Plural refrigerant
system
Confirm supply power
connector CN40 of outdoor unit
Only 1 set with
CN40 inserted?
Modification of CN40
insertion method
* For the investigation method, follow
<Investigation method of transmission wave
shape/noise>.
Modification of faulty
point
Investigation of the
cause of noise
Replace insertion
of CN40 to CN41
Shut off the power source of outdoor/
indoor units and make it again.
Erroneous power
source work
Erroneous transmis-
sion work
MELANS connected
system
Confirm supply power
connector CN40 of outdoor unit
YES
NO
YES
NO
NO
YES
NO
YES
NO
YES
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...