–174–
Checking
code
6607
(continued)
Meaning, detecting method
No ACK error
When no ACK signal is detected in 6 continuous times with 30 second interval by transmission side
controller, the transmission side detects error.
Note) The address/attribute shown on remote controller indicates the controller not providing
the answer (ACK).
Checking method & countermeasure
System
compo-
sition
Generating
unit address
Display of
trouble
Detecting
method
Cause
(2) Group oper
ation system using plur
al refr
igerants
1
Outdoor
unit
(OC)
2
Indoor
unit (IC)
3
Remote
control-
ler (RC)
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
No reply
(ACK) at IC
transmission
to OC
No reply
(ACK) at RC
transmission
to IC
No reply
(ACK) at IC
transmission
to RC
As same that for single refrigerant system.
1) Cause of 1) ~ 5) of “Cause for single refriger-
ant system”.
2) Slipping off or short circuit of transmission line
of OC terminal block for centralized control
(TB7).
3) Shut down of OC unit power source of one re-
frigerant system.
4) Neglecting insertion of OC unit power supply
connector (CN40).
5) Inserting more than 2 sets of power supply
connector (CN40) for centralized control use.
For generation after normal operation conduct-
ed once, the following causes can be consider-
ed.
• Total capacity error
(7100)
• Capacity code setting error
(7101)
• Connecting set number error (7102)
• Address setting error
(7105)
6) The transmission booster is defective, has dis-
connected wires, or the power has been cut-
off.
1) Cause of 1) ~ 3) of “Cause for single refri-
gerant system”.
2) Slipping off or short circuit of transmission line
of OC terminal block for centralized con-trol
(TB7).
3) Shut down of OC unit power source of one
refrigerant system.
4) Neglecting insertion of OC unit power supply
connector (CN40).
5) Inserting more than 2 sets of power supply
connector(CN40) for centralized control use.
At generation after normal operation conducted
once, the following causes can be considered.
• Total capacity error
(7100)
• Capacity code setting error
(7101)
• Connecting set number error (7102)
• Address setting error
(7105)
6) The transmission booster is defective, has dis-
connected wires, or the power has been cut-
off.
Same as measure for single refrigerant
system.
a) Shut down the power source of both
IC and OC for over 5 minutes simul-
taneously, and make them again.
Normal state will be returned in-
case of accidental trouble.
b) Check for 1) ~ 6) of causes. If cause
is found, remedy it.
c) Check other remote controller or OC
unit LED for troubleshooting for
trouble.
Trouble
→
Modify the trouble ac-
cording to the content
of check code.
No trouble
→
Faulty indoor control-
ler
a) Shut down the power source of OC
for over 5 minute, and make it again.
Normal state will be returned in case
of accidental trouble.
b) Check for 1) ~ 6) of causes. If cause
is found, remedy it.
When normal state can not be ob-
tained, check 1) ~ 6) of causes.
Содержание CITY MULTI PUHY-400YMF-B
Страница 13: ... 10 Noise filter NF DC reactor DCL Noise filter box Noise Filter Box Rear of the controller box ...
Страница 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Страница 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Страница 20: ... 17 CONT board SWU2 CNTR SWU1 CNFC1 SW3 SW2 CNS1 M NET transmission CN20 Power supply 1 N 3 L1 ...
Страница 26: ... 23 ...
Страница 50: ... 47 ...
Страница 152: ... 149 Model PUHY 400YMF B 500YMF B ...