- 183 -
[
IX
Troubleshooting ]
Error Code
Error definition and error
detection method
Cause
Check method and remedy
1102
Abnormal dis-
charge air tem-
perature
1.If the discharge tem-
perature of 120°C
[248°F] or more is de-
tected during the
above operation (the
first detection), the
heat source unit stops
once, turns to anti-re-
start mode for 3 min-
utes, and restarts after
3 minutes automati-
cally.
2.If the discharge tem-
perature of 120°C
[248°F] or more is de-
tected again (the sec-
ond detection) within
30 minutes after the
second stop of the
heat source unit de-
scribed above, the
mode will be changed
to 3-minute restart
mode, then the heat
source unit will restart
in 3 minutes.
3.If the discharge tem-
perature of 120°C
[248°F] or more is de-
tected (the third detec-
tion) within 30 minutes
after the stop of the
heat source unit de-
scribed above (re-
gardless of the first or
the second stop), the
heat source unit will
make an error stop,
and the error code
"1102" will be dis-
played.
4.If the discharge tem-
perature of 120°C
[248°F] or more is de-
tected more than 30
minutes after the pre-
vious stop of the heat
source unit, the detec-
tion is regarded as the
first detection, and the
operation described in
step 1 above will start.
5.For 30 minutes after
the stop (the first stop
or the second stop) of
the heat source unit,
preliminary errors will
be displayed on the
LED display.
(1) Gas leak, gas shortage
Refer to the page on refrigerant
amount evaluation.
(2) Overload operation
Check operating conditions and op-
eration status of indoor/heat source
units.
(3) LEV failure on the indoor
unit
(4) Heat source unit LEV1
malfunction
(5) Solenoid valve malfunc-
tion (SV4a-4d)
-> Heating
Perform a cooling or heating opera-
tion and check the operation.
Cooling : LEV on the indoor unit,
LEV1
Heating : LEV on the indoor unit,
SV4a-4d
Refer to the section "Troubleshoot-
ing the LEV and solenoid valve."
(6) Closed ball valve
Confirm that the ball valve is fully
open.
(7) Insufficient heat source
water supply, heat source
water supply cutoff, dirty or
clogged water heat ex-
changer
-> Heating
Items (3)-(7) are caused
by a rise in the discharge
temperature due to a drop
in pressure.
Check for dirty or clogged water heat
exchanger
Check the heat source water pump
(8) Gas leak between low and
high pressures
(4-way valve failure, com-
pressor failure, solenoid
valve (SV1) failure)
Perform a cooling or heating opera-
tion and check the operation.
(9) Thermistor failure
(TH1)
Check the thermistor resistor.
(10) Input circuit failure on the
controller board thermistor
Check the inlet air temperature on
the LED monitor.
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...