- 242 -
[
IX
Troubleshooting ]
(3) System connected to the system controllers (MELANS)
Error Code
Error definition and error detection method
6607
(Contin-
ued)
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
Heat
source
unit
(OC)
M-NET re-
mote control-
ler (RC)
System con-
troller (SC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at
BC trans-
mission to
OC
Same cause as that for system with
one heat source unit
Same remedy as that for system with one
heat source unit
BC control-
ler (BC)
M-NET re-
mote control-
ler (RC)
system con-
troller (SC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at IC
transmis-
sion to BC
Same cause as that for system with
one heat source unit
Same remedy as that for system with one
heat source unit
Indoor
unit
(IC)
M-NET re-
mote con-
troller (RC)
No acknowl-
edgement
(ACK) at RC
transmission
to IC
Same as grouping of units in a sys-
tem with multiple heat source units
Same remedy as that for grouping of units in
a system with multiple heat source units
system
controller
(SC)
No ac-
knowl-
edgement
(ACK) at
SC trans-
mission to
IC
1. Error occurrence on some IC
(1) Same cause as that for system
with one heat source unit
Same remedy as that for system with
one heat source unit
2. Error occurrence on all IC in the
system with one heat source unit
(1) Total capacity error (7100)
(2) Capacity code error (7101)
(3) Error in the number of connected units
(7102)
(4) Address setting error (7105)
(5) Disconnection or short circuit of the
transmission line for the heat source
unit on the terminal block for central-
ized control line connection (TB7)
(6) Turn off the power source of the heat
source unit
(7) Malfunction of electrical system for the
heat source unit
1) Check the LED display for troubleshoot-
ing on the heat source unit.
->If an error is found, check the check
code definition, and correct the error.
->If no error is found, check 2).
2) Check (5) - (7) on the left.
3. Error occurrence on all IC
(1) Same causes as (1) - (7) described in
2.
(2) The male power supply connectors on
2 or more heat source units are con-
nected to the female power supply
switch connector (CN40) for the trans-
mission line for centralized control.
(3) Disconnection or shutdown of the pow-
er source of the power supply unit for
transmission line
(4) System controller (MELANS) malfunc-
tion
Check voltage of the transmission line for
centralized control.
20V or more : Check (1) and (2) on the
left.
Less than 20V : Check (3) on the left.
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...