- 54 -
[
II
Restrictions ]
1. PQHY
(1) Line branching
Unit: m [ft]
Operation
Pipe sections
Allowable length of
pipes
Length
Total pipe length
A+B+C+D
+a+b+c+d+e
300 [984] or less
Total pipe length (L) from the heat source unit to
the farthest indoor unit
A+B+C+D+e
150 [492] or less
Total pipe length from the first branch to the far-
thest indoor unit ( )
B+C+D+e
40 [131] or less
Height
difference
Between indoor and
heat source units
Heat source unit above
indoor unit
H
50 [164] or less
Heat source unit below
indoor unit
H'
40 [131] or less
Between indoor units
h
15 [49] or less
Heat source unit
L
H
H'
A
A
B
C
D
a
b
c
d
h
e
First branch
Indoor
Indoor
Indoor
Indoor
Indoor
5
1
2
3
4
Note : "Total sum of downstream unit model numbers"
in the table is the sum of the model numbers
of the units after point A in the figure.
To downstream units
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...