- 244 -
[
IX
Troubleshooting ]
(3) System connected to the system controllers (MELANS)
Error Code
Error definition and error detection method
6607
(Contin-
ued)
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
System
controller
(SC)
M-NET re-
mote con-
troller (RC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at IC
transmis-
sion to SC
1. Error display on some displays on
M-NET remote controllers
(1) Faulty wiring of the transmission
line for M-NET remote controller
(2) Disconnection or contact failure
of the transmission connector for
M-NET remote controller
(3) M-NET remote controller failure
Check (1) - (3) on the left.
2. Error occurrence on all IC in the
system with one heat source unit
(1) An error is found by the heat
source unit.
Total capacity error (7100)
Capacity code error (7101)
Error in the number of connect-
ed units (7102)
Address setting error (7105)
(2) Disconnection or short circuit of
the transmission line for the heat
source unit on the terminal block
for centralized control line con-
nection (TB7)
(3) Turn off the power source of the
heat source unit.
(4) Malfunction of electrical system
for the heat source unit
1) Check the LED display for troubleshoot-
ing on the heat source unit.
->If an error is found, check the check
code definition, and correct the error.
->If no error is found, check 2).
2) Check (2) - (4) on the left.
3. Error display on all displays on M-
NET remote controllers
(1) Same causes as (1) - (4) de-
scribed in 2.
(2) The male power supply connec-
tor on the heat source unit is
connected to the female power
supply switch connector (CN40)
for the transmission line for cen-
tralized control.
(3) Disconnection or shutdown of
the power source of the power
supply unit for transmission line
(4) System controller (MELANS)
malfunction
Check (1) - (4) on the left.
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...