- 254 -
[
IX
Troubleshooting ]
Phenomena
Cause
3
"HO" or "PLEASE WAIT" dis-
play on the remote controller
does not disappear, and no op-
eration is performed even if the
button is pressed. ("HO" or
"PLEASE WAIT" display will
normally turn off 5 minutes lat-
er after the power on.)
1.The power for the M-NET transmission line is not supplied from the heat source
unit.
2.Short-circuited transmission line
3.Incorrect wiring of the M-NET transmission line on the heat source unit.
Disconnected wire for the MA remote controller or disconnected line to the ter-
minal block.
The indoor transmission line is connected incorrectly to the transmission termi-
nal block for centralized controller (TB7).
The male power supply connectors on the multiple heat source units are con-
nected to the female power supply switch connector (CN40).
In the system to which the power supply unit for transmission lines is connect-
ed, the male power supply connector is connected to the female power supply
switch connector (CN40) on the heat source unit
4.Disconnected M-NET transmission line on the indoor unit.
5.Disconnected wire between the terminal block for M-NET line (TB5) of the indoor
unit and the indoor unit board (CN2M) or disconnected connector.
6.Incorrect wiring for the MA remote controller
Short-circuited wire for the MA remote controller
Disconnected wire for the MA remote controller (No.2) and disconnected line
to the terminal block.
Reversed daisy-chain connection between groups
Incorrect wiring for the MA remote controller to the terminal block for transmis-
sion line connection (TB5) on the indoor unit
The M-NET transmission line is connected incorrectly to the terminal block
(TB13) for the MA remote controller.
7.The sub/main setting of the MA remote controller is set to sub.
8.2 or more main MA remote controllers are connected.
9.Indoor unit board failure (MA remote controller communication circuit)
10.Remote controller failure
When 2. and 3. apply, check code 7102 will be displayed on the self-diagno-
sis LED.
Check method and remedy
YES
YES
YES
NO
NO
YES
YES
NO
NO
NO
Check the self-diagnosis LED
Error found?
Error found?
Replace the M-NET remote
controller with the MA
remote controller
Check for 5 and 6.
17 - 30V?
Same symptom for all units in a
system with one outdoor unit?
Check (1).
Check
2 and 3.
Check 4.
Correct
the error.
Correct
the error.
Measure voltages of the
terminal block for transmission
line (TB5) on the indoor unit.
Refer to [4].6.(2) "Heat source unit transmission power
source circuit failure judgment" for the check method.
Is the error code 7102
displayed?
Indoor unit board or
MA remote controller failure
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...