- 25 -
[
II
Restrictions ]
Wiring method/address setting method
1) Indoor/outdoor (heat source) transmission line
Daisy-chain terminals M1 and M2 on the terminal block for indoor-outdoor (heat source) transmission line (TB3) on
the outdoor (heat source) unit (OC), terminals M1 and M2 of the terminal block for indoor-outdoor (heat source)
transmission line (TB02) on the BC controller (BC), and terminals M1 and M2 on the terminal block for indoor-out-
door (heat source) transmission line (TB5) on each indoor unit (IC). (Non-polarized 2-core cable)
Only use shielded cables.
[Shielded cable connection]
To ground the shielded cable, daisy-chain the ground terminal ( )on the outdoor (heat source) unit (OC), S termi-
nals on the terminal block (TB3) on the terminal block (TB1) on the BC controller (BC), and the S terminal on the
terminal block (TB5) on the indoor unit (IC).
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Connect terminals 1 and 2 on the terminal block for MA remote controller line (TB15) on the indoor unit (IC) to the
terminal block on the MA remote controller (MA). (Non-polarized 2-core cable)
MA remote controllers can be connected to the indoor units of type C or later.
[When 2 remote controllers are connected to the system]
When 2 remote controllers are connected to the system, connect terminals 1 and 2 of the terminal block (TB15) on
the indoor unit (IC) to the terminal block on the two MA remote controllers.
Set one of the MA remote controllers to sub. (Refer to MA remote controller function selection (4 [3]2.) or the in-
stallation manual for the MA remote controller for the setting method.)
[Group operation of indoor units]
To perform a group operation of indoor units (IC), daisy-chain terminals 1 and 2 on the terminal block (TB15) on all
indoor units (IC) in the same group, and then connect terminals 1 and 2 on the terminal block (TB15) on the indoor
unit on one end to the terminal block on the MA remote controller. (Non-polarized 2-core cable)
To perform a group operation of indoor units that have different functions, refer to [4] 2.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block (TB5) on the indoor unit (IC) to the appropriate terminals on
the terminal block for indoor-outdoor (heat source) transmission line (TB5) on LOSSNAY (LC). (Non-polarized 2-
core cable)
Interlock operation setting with all the indoor units in the same system will automatically be made.
Refer to "[4] 2. Manual address setup for both indoor and outdoor (heat source) units" in the following cases: per-
forming an interlock operation of part of the indoor units in the system with a LOSSNAY unit, using LOSSNAY
alone without interlocking it with any units, performing an interlock operation of more than 16 indoor units with a
LOSSNAY unit, or connecting two or more LOSSNAY units to indoor units in the same system.
5) Switch setting
No address settings required.
Pro
ce-
du-
res
Unit or controller
Address
setting
range
Setting method
Notes
Facto-
ry set-
ting
1
Indoor
unit
Main unit
IC
No settings
required.
-
Port number setting is re-
quired by an R2 or WR2
system.
To perform a group opera-
tion of indoor units that
have different functions,
refer to [4] 2.
00
Sub unit
IC
2
LOSSNAY
LC
No settings
required.
-
00
3
MA
remote
controller
Main
remote
controller
MA
No settings
required.
-
Main
Sub
remote
controller
MA
Sub
remote
controller
Settings to be made ac-
cording to the remote con-
troller function selection
4
Outdoor (heat source)
unit
OC
No settings
required.
-
00
5
Auxiliary
unit
BC
controller
BC
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...