- 239 -
[
IX
Troubleshooting ]
(1) System with one heat source unit
Error Code
Error definition and error detection method
6607
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
Heat
source
unit
(OC)
M-NET re-
mote con-
troller (RC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at
BC trans-
mission to
OC
(1) Contact failure of transmission line
of OC or BC
(2) Decrease of transmission line volt-
age/signal by exceeding accept-
able range of transmission wiring .
Farthest :
200 m [656ft] or less
Remote controller wiring: 10m
[32ft] or less
(3) Erroneous sizing of transmission
line (Not within the range below).
Wire diameter: 1.25mm
2
[AWG16] or more
(4) Heat source unit main board fail-
ure
(5) Power circuit failure of heat
source unit
Turn off the power source of the heat source
unit, and turn it on again. If the error is acci-
dental, it will run normally.
If not, check the causes (1) - (5).
Refer to 9.[4].-7-.(2) "Heat source unit trans-
mission power source circuit failure judg-
ment" for (5).
BC control-
ler (BC)
M-NET re-
mote con-
troller (RC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at IC
transmis-
sion to BC
(1) When BC controller address is
changed or modified during opera-
tion.
(2) Faulty or disconnected transmis-
sion wiring of BC controller
(3) Disconnected connector of BC
controller (CN02)
(4) Faulty control board of BC control-
ler
Turn off the heat source/indoor units for 5 or
more minutes, and turn them on again.
If the error is accidental, they will run nor-
mally. If not, check the causes (1) - (4).
Indoor
unit
(IC)
M-NET re-
mote con-
troller (RC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at
RC trans-
mission to
IC
(1) When IC unit address is changed
or modified during operation.
(2) Faulty or disconnected IC trans-
mission wiring
(3) Disconnected IC connector
(CN2M)
(4) Indoor unit board failure
(5) M-NET remote controller failure
Turn off the heat source/indoor units for 5 or
more minutes, and turn them on again.
If the error is accidental, they will run nor-
mally. If not, check the causes (1) - (5).
LOSSNAY
(LC)
M-NET re-
mote con-
troller (RC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at IC
transmis-
sion to LC
(1) The power source of LOSSNAY
has been shut off.
(2) When the address of LOSSNAY is
changed in the middle of the oper-
ation
(3) Faulty or disconnected transmis-
sion wiring of LOSSNAY
(4) Disconnected connector (CN1) on
LOSSNAY
(5) Controller failure of LOSSNAY
Turn off the power source of LOSSNAY and
turn it on again. If the error is accidental, it
will run normally.
If not, check the causes (1) - (5).
M-NET re-
mote con-
troller (RC)
M-NET re-
mote con-
troller (RC)
No ac-
knowl-
edgement
(ACK) at IC
transmis-
sion to RC
(1) Faulty transmission wiring at IC
unit side.
(2) Faulty wiring of the transmission
line for M-NET remote controller
(3) When the address of M-NET re-
mote controller is changed in the
middle of the operation
(4) M-NET remote controller failure
Turn off the power source of the heat source
unit for 5 minutes or more, and turn it on
again. If the error is accidental, it will run
normally. If not, check the causes (1) - (4).
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...