- 81 -
[
IV
Remote Controller ]
IV
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers
There are two types of remote controllers: M-NET (ME) remote controller, which is connected on the indoor-outdoor (heat
source) transmission line, and MA remote controller, which is connected to each indoor unit.
1. Comparison of functions and specifications between MA and ME remote controllers
2. Remote controller selection criteria
MA remote controller and M-NET remote controller have different functions and characteristics. Choose the one that better
suits the requirements of a given system. Use the following criteria as a reference.
Functions/specifications
MA remote controller
*1*2
*1. MA remote controller refers to MA remote controller, MA simple remote controller, and wireless remote controller.
*2. Either the MA remote controller or the M-NET remote controller can be connected when a group operation of units in a
system with multiple outdoor (heat source) units is conducted or when a system controller is connected.
M-NET (ME) remote controller
*2*3
*3. M-NET remote controller refers to ME remote controller.
Remote controller address settings Not required
Required
Indoor/outdoor (heat source) unit
address settings
Not required (required only by a system
with one outdoor (heat source) unit)
*4
*4. Depending on the system configuration, some systems with one outdoor (heat source) unit may require address settings.
Required
Wiring method
Non-polarized 2-core cable
∗
To perform a group operation, dai-
sy-chain the indoor units using
non-polarized 2-core cables.
Non-polarized 2-core cable
Remote controller connection
Connectable to any indoor unit in the
group
Connectable anywhere on the indoor-out-
door (heat source) transmission line
Interlock with the ventilation unit
Each indoor unit can individually be in-
terlocked with a ventilation unit. (Set up
via remote controller in the group.)
Each indoor unit can individually be inter-
locked with a ventilation unit. (Set up via
remote controller.)
Changes to be made upon group-
ing change
MA remote controller wiring between in-
door units requires rewiring.
Either the indoor unit address and remote
controller address must both be changed,
or the registration information must be
changed via MELANS.
MA remote controller
*1*2
M-NET (ME) remote controller
*1*2
There is little likelihood of system expansion and
grouping changes.
Grouping (floor plan) has been set at the time of in-
stallation.
There is a likelihood of centralized installation of re-
mote controllers, system expansion, and grouping
changes.
Grouping (floor plan) has not been set at the time of
installation.
To connect the remote controller directly to the OA
processing unit.
*1. M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
*2. A system controller must be connected to a system to which both MA remote controller and M-NET remote controller are
connected.
<System with MA remote controller>
<System with M-NET remote controllers>
MA remote controller
Heat source unit
Indoor unit
M-NET transmission line
(indoor/outdoor (heat source) transmission line)
group
group
M-NET remote controller
Heat source unit
Indoor unit
M-NET transmission line
(indoor/outdoor (heat source) transmission line)
group
group
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...