- 215 -
[
IX
Troubleshooting ]
7110
Heat source
unit
Unset unit connection
information error
The start-up of the unit
has not completed nor-
mally in the system to
which a transmission
booster is connected.
When all power sources are
turned off after the start-up of
the unit has completed normal-
ly.
When the start-up of the unit
has completed without turning
on the power source of the
transmission booster.
When the power source of the
transmission booster is turned
on afterwards.
1) Check whether the power
source of the transmission is
turned on.
2) Turn off the power sources of
heat source/indoor units and
transmission booster, and turn
them on again.
7111
Indoor unit
OA processing
unit
Remote controller sen-
sor failure
This error occurs when
the temperature data is
not sent although the re-
mote controller sensor is
specified.
The remote controller without
the temperature sensor (the
wireless remote controller or
the M-NET compact remote
controller (mounted type)) is
used and the remote controller
sensor for the indoor unit is
specified. (SW1-1 is ON.)
Replace the remote controller with
the one with built-in temperature
sensor.
7113
Heat source
unit
Model setting error
(short detection)
Short-circuit
Faulty wiring or contact failure
Check all main board connectors
and rectify faulty connection.
7117
Heat source
unit
Model setting error
(Open detection)
Disconnected connector, dis-
connected wire, or contact fail-
ure
Check for the contact of the connec-
tor CNTYP1, 4, 5 on the main board.
7130
Heat source
unit
Incompatible units
The check code will ap-
pear when the indoor
units with different refrig-
erant systems are con-
nected.
The indoor unit that uses only
R22 refrigerant is connect-
ed.The wrong unit model is
connected.
When connecting Mr. SLIM (A
control) with M-NET, the con-
necting adapter for M-NET
must be connected to the in-
door unit.
Check the connected indoor unit
model.
Check whether the connecting
adapter for M-NET is not connected
to the indoor unit.
(Connect the connecting adapter for
M-NET to the heat source unit.)
Error
Code
Error source
Error definition and error
detection method
Cause
Check method and remedy
Содержание City Multi CMB-P1016NU-G
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 86: ... 77 III Heat Source Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 112: ... 103 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 105 2 Principal Parts and Functions 109 ...
Страница 113: ... 104 ...
Страница 117: ... 108 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 129: ... 120 ...
Страница 163: ... 154 ...
Страница 165: ... 156 ...
Страница 187: ... 178 ...
Страница 312: ... 303 X LED Monitor Display on the Heat Source Unit Board 1 How to Read the LED on the Service Monitor 305 ...
Страница 313: ... 304 ...