background image

– 13 –

<Maintenance>

Backup (P95)

Import (P97)

Touch Panel Calibration (P103)

Touch [Start calibration]

“Calibration completed.” or

“No operation for one minute.”

CSV output (P100)

Calibration (P103)

WT05369X15.book  Page 13  Wednesday, November 7, 2012  10:33 AM

Содержание AG-150A

Страница 1: ... 5 Setting the Basic Information 58 7 6 Network Setting 60 7 7 Group Setting 64 7 8 Interlocked Setting 68 7 9 Block Setting 70 7 10 Floor Layout Setting 72 7 11 Checking the refrigerant systems 77 7 12 Advanced settings 78 8 Function 1 81 8 1 Measurement Setting 81 9 Function 2 87 9 1 External temperature interlock 87 9 2 Night setback function 90 10 User Setting 93 10 1 Setting the Maintenance U...

Страница 2: ...ry Stop the operation immediately and notify your dealer if an error code is displayed and the controller does not operate or when any abnormality is noticed Continuing the operation may result in damage to the controller or fire Do not install the controller where there is a risk of leaking flammable gas If the leaked gas accumulates around the controller it may ignite and cause an explosion Do n...

Страница 3: ...he smallest unit that the AG 150A and AG 150A A can control The maximum number of units and controllers that each group can contain is 16 Block Block is a group of groups Energy save and peak cut settings are made for each block EC EC is short for Expansion Controller PAC YG50ECA Hereinafter AG 150A and AG 150A A unless otherwise specified will be called AG 150A ...

Страница 4: ... operation 19 28 C 67 83 F Setting temperature range for Air To Water PWFY Booster unit 3 Heating 30 50 C 87 122 F Heating ECO 30 45 C 87 113 F Hot Water 30 70 C 87 158 F Anti freeze 10 45 C 50 113 F Cooling Invalid Setting temperature for HWHP CAHV Heating 25 70 C 77 158 F Heating ECO Invalid Hot Water 25 70 C 77 158 F Anti freeze Invalid Water HEX unit 3 Heating 30 45 C 87 113 F Heating ECO 30 4...

Страница 5: ...aster Sub setting to be made Enables disables the Seasonal schedule settings Groups This function is used to register indoor units LOSSNAY units DIDO controller PAC YG66DCA Air To Water PWFY HWHP CAHV remote controllers and lower level system controllers to a group Blocks This function is used to register a group to a block Interlock This function is used to interlock the operation of indoor units...

Страница 6: ...ttings and interlock settings can only be made from a Main controller Sub system controller Sub SC Sub controller refers to a system controller that is controlled including the units it controls by a Main system controller AG 150A M NET Gateway management range Another system controller management range Unit Unit Unit Unit When AG 150A controls another system controller or when the system contains...

Страница 7: ...ot lit All groups are stopped Lit One or more groups of the units are ON not including the general equipments connected to PAC YG66DCA Blinking Indicates that an error occurred including all connected equipments Display Touch panel Note Before using the AG 150A remove the protective sheet on the surface cover CAUTION If the protective sheet is left on the screen the sheet may stick to the LCD and ...

Страница 8: ...ntact the service center Touching two points simultaneously will be interpreted as pressing a different point To avoid malfunctions only touch one point at a time Login P52 Touch Login Advanced settings screen P78 Date and time P56 Unit Info P58 License P57 Groups P64 Network P60 Interlock P68 Floor Layout P72 Blocks P70 The above nine initial setting screens can be accessed from the sub menu Syst...

Страница 9: ...en P29 Floor layout detailed icons P26 Floor layout simplified icons P27 Block display P27 Login P52 Touch Touch Touch Measurement display P27 With connection to AI and PI controllers HWHP display P27 HWHP operation screen P33 With connection to HWHP CAHV units ...

Страница 10: ...creen P38 Schedule setting screen block display Weekly P36 Schedule setting screen floor layout Weekly P35 Schedule setting screen air conditioning units P39 Login P52 Touch With connection to HWHP CAHV units With connection to HWHP CAHV units Schedule setting screen HWHP display Weekly P37 ...

Страница 11: ...edule setting screen block display Ex Weekly 1 2 3 4 5 P41 Schedule setting screen floor layout Ex Weekly 1 2 3 4 5 P41 Schedule setting screen HWHP CAHV display Ex Weekly 1 2 3 4 5 P41 Season setting screen P43 Weekly schedule screen P38 Schedule setting screen air conditioning units P39 Annual schedule pattern setting screen P44 Touch Touch ...

Страница 12: ...atus List Log Malfunction P48 Filter sign P50 Login P52 Touch Touch Touch Filter Sign Touch Malfunction Unit error P51 Communication error P51 Login P52 Touch Communication Error Touch Touch Unit Error Touch ...

Страница 13: ...nction 1 Function 2 User Info Measurement P81 Touch Setback Touch Ext Temp Interlock Ext Temp Interlock P87 Setback P90 Touch Building Manager Touch Maintenance User Maintenance User P93 Building Manager P94 ...

Страница 14: ... 13 Maintenance Backup P95 Import P97 Touch Panel Calibration P103 Touch Start calibration Calibration completed or No operation for one minute CSV output P100 Calibration P103 ...

Страница 15: ...s on how to set the date and time The initial setup sequence does not set the date and time correctly Be sure to manually set the correct date and time Touch the Save Settings button to reflect the changes Touch Unit Info After setting the date and time touch the Unit Info tab and set the Name and Unit ID Be sure to set the Expansion Controller setting to Do not use Refer to Section 7 5 for the de...

Страница 16: ...ch the on the top right hand of the screen to go into the Operation Monitor screen Configure the floor layout on the Floor Layout screen if necessary When the unit is started up again the Operation Monitor instead of the Initial Settings screen will appear To change certain settings refer to Section 7 1 Calling up the initial setting screen to change the settings After moving to the Operation Moni...

Страница 17: ...et the IP address for the AG 150A Select the Expansion controller EC1 EC3 whose settings are to be made from the tab menu Check that the DB No on the AG 150A itself and the DB No of the Expansion Controller match The DB No for the AG 150A can be found on the back of the controller on the package box or on the LCD Refer to Section 7 1 P 52 for how to confirm the DB No on the LCD The DB No for the E...

Страница 18: ...ut screen if necessary When the unit is started up again the Operation Monitor instead of the Initial Settings screen will appear To change certain settings refer to Section 7 1 Calling up the initial setting screen to change the settings The Date and Time setting screen will appear Set the date and time Refer to Section 7 3 for the details on how to set the date and time To synchronize the time w...

Страница 19: ...er moving to the Operation Monitor screen the startup screen will appear Startup takes a maximum of five minutes after the message appears It takes about two to three minutes when no communication errors occur ...

Страница 20: ...cted to a system Use only one AG 150A to make group settings for other units When multiple AG 150A controllers are connected to a system the following functions should be used only on one of the AG 150A controllers License registration schedule settings Schedule Not Available energy save peakcut Night Setback Control Interlock External Temperature Interlock Night Mode Schedule System changeover an...

Страница 21: ... 150A PAC SC51KUA and start the initial setting process Make the initial settings for each AG 150A 1st AG 150A Master 2nd and subsequent AG 150A units 7 Select the display language 7 Select the display language 8 Make the unit information settings 8 Make the unit information settings Set the Use Do not use setting for the Expansion controller to Use Set the Use Do not use setting for the Expansion...

Страница 22: ...ed will be displayed for a few minutes 11 Make the settings for the group names and unit addresses 11 Make the settings for the general equipment and group name A group name different from the first unit master may be assigned Check that the group settings are the same as the ones made for the first unit master Re enter the same settings for the general equipment as the ones for the first unit mas...

Страница 23: ...as the settings for the Master unit 14 Make the settings for the floor layout 14 Make the settings for the floor layout The settings for the 2nd and subsequent units do not need to be the same as the settings for the Master unit 15 Set the clock 15 Set the clock 16 The initial Time Master Sub setting is Master Leave the setting as it is 16 Set the Time Master Sub setting to Sub ...

Страница 24: ... 23 17 Initial settings are completed 17 Initial settings are completed Perform a test run to check for proper settings Perform a test run to check for proper settings ...

Страница 25: ...els have different functions available Measurement display screens Displays the measurement status by the temperature sensor humidity sensor and watt hour meter Displayed only when an AI controller and a PI controller are connected and a temperature sensor humidity sensor and watt hour meter are used HWHP CAHV display screens Displays the ON OFF status operation status and water temperatures of Ho...

Страница 26: ... is accessed from the Block display screen Press Block Press Block Press Floor Press OK or Cancel Applicable only when the operation screen is accessed from the Floor display screen Select a group and press Operate Refer to Section 6 1 Operation condition monitoring P 26 Block button Zoom out button Zoom in button Operation button Floor button Operation button Cancel button OK button Block display...

Страница 27: ...rror Indicates the number of units that are in error The following icons indicate the operation status If there is a device that cannot be identified will appear over the icon of the device Selecting the group icon and then pressing the operation button will take the screen to the operation screen for the selected group If more than one groups exist within a group such as air conditioning unit gro...

Страница 28: ... the ON OFF temperature fan speed air flow direction prohibit permit status of the remote controller operation mode and Schedule Available Not Available can be checked Press the scroll button to see the status of the rest of the blocks Several types of icons will appear Block display Scroll button Block selection button Selects a block of groups Block selected Block deselected Displays the measure...

Страница 29: ...chedule setting Not Available During energy save control and During night setback will be displayed only on the AG 150A controller that is executing these functions The energy saving icon is displayed while the energy saving control is performed in a group of indoor units and in the outdoor unit belonged to that group If a given LOSSNAY unit is interlocked with multiple indoor unit groups the LOSS...

Страница 30: ...ow increases decreases the temperature by one degree respectively The settable temperature range depends on the mode and model If the Up arrow is pressed when the upper limit temperature is displayed the lower limit temperature will appear and the Down arrow vice versa Depending on the model details the temperature range may change and Auto setting may not be available If operation modes and prese...

Страница 31: ...n mode temperature and filter sign reset Pressing of each button toggles through the following three options Retention of current status Permit Prohibit 7 Schedule Available Not Available Select the Available Not Available status for the schedule settings The Available Not Available status changes with each pressing of the button 8 Filter sign reset Press Reset under Filter Sign Filter cleaning wa...

Страница 32: ...current status Permit Prohibit 5 Schedule Available Not Available Select the Available Not Available status for the schedule settings The Available Not Available status changes with each pressing of the button 6 Filter sign reset Press Reset under Filter Sign Filter cleaning warning sign will be cleared Cumulative operation time is reset 7 OK Press the OK button to reflect the change Pressing the ...

Страница 33: ... 30 C 50 87 F Temperatures are displayed Fahrenheit if Fahrenheit is selected 4 Prohibiting local remote controller operation Press the button that corresponds to each of the following buttons to permit or prohibit access to these functions ON OFF operation mode temperature and circulating water replacement sign reset Pressing of each button toggles through the following three options Retention of...

Страница 34: ... button to reflect the change Pressing the OK button saves the setting and takes the screen back to the previous screen Floor layout or Block display 4 Cancel Press the Cancel button to cancel the change Pressing the Cancel button cancels the change and takes the screen back to the previous screen Floor layout or Block display Function Operation method Display 1 ON OFF Select the operation status ...

Страница 35: ...n while the unit is stopped 5 Prohibiting local remote controller operation Press the button that corresponds to each of the following buttons to permit or prohibit access to these functions ON OFF operation mode and temperature Pressing of each button toggles through the following three options Retention of current status Permit Prohibit 6 Schedule Available Not Available Select the Available Not...

Страница 36: ...0 and set an Enable operation for 23 59 Note The weekly schedules of the groups whose schedule settings are Not Available from the control screen will not be executed Refer to section 6 2 1 Select the type of schedule settings to make 1 1 Group 1 2 Floor Copy destination frame A pale orange frame appears around the copy destination unit Item selection frame An orange frame appears around the selec...

Страница 37: ... at the right bottom corner of the screen to bring up the weekly schedule screen Select All Units button Equipment type selection screen If more than one groups exist within a group such as air conditioning unit group ventilation unit LOSSNAY group and Other Equipment group a screen to select a group will appear when the Set button is touched Booster unit and Water HEX unit will appear as Air To W...

Страница 38: ...ectable Orange frames will appear around the icons of the selected groups To deselect a selected group touch the icon again To deselect all selected groups touch the deselect all button Touching the Edit button at the right bottom corner of the screen after selecting one or more groups will display the weekly schedule setting window for the HWHP units Each group will be displayed with an icon and ...

Страница 39: ...eed to be made The settings for only the operation mode or the setting temperature for example can be made Note When setting a schedule for all groups or for a block it is possible to set all operation modes such as Auto mode etc but if some targeted air conditioner units do not have such a function then those units will not run in the specified mode When setting the schedule consider what functio...

Страница 40: ...er PWFY and LOSSNAY have no Optimized Start function To copy the schedule of a given day to another day select the days of the week from the weekly schedule setting screen touch Copy to select it select a day to copy the schedule to and touch Paste To copy the weekly schedule for one group to another group select the group from the weekly schedule setting screen Floor layout or block display scree...

Страница 41: ...mperature sensor the temperature may not be correct when the air conditioner is inactive and the air is not fresh When the temperature is not measured correctly switch the sensor to external temperature sensor PAC SE40TSA or remote control sensor Select the mode Optimized Start on the schedule setting screen when this function is required 9 00 8 45 9 00 8 40 Room temperature Ex Pre cooling Setting...

Страница 42: ...ting a schedule that is only for a particular day be sure to set your schedule in a way that will not impact on the next day s operation For example if you wish to prohibit operations being performed from the remote controller after 17 00 set a Prohibit operation for 17 00 and set an Enable operation for 23 59 Note The weekly schedules of the groups whose schedule settings are Not Available from t...

Страница 43: ... set prohibit remote controller items individually When allowing remote controller operation under K control however all items must be set enable Note Configurable settings depend on the type of group Air Conditioner group LOSSNAY group Air To Water PWFY group general equipment group and HWHP CAHV group Note When setting a schedule for ventilator units the temperature setting is not displayed More...

Страница 44: ...ng screen has three pages The current page can be checked at the lower left The period setting can go past 12 31 i e 11 1 3 31 If the applicable periods for Weekly 1 through Weekly 5 overlap the highest priority schedule will be executed based on the following priority order Weekly 1 Weekly 2 Weekly 3 Weekly 4 Weekly 5 If the Season setting is set to Not Available on the Advanced settings screen t...

Страница 45: ...ngs for the date in the annual schedule Note When the contents of an operation are executed as part of a schedule these contents will continue to be in effect until they are changed by a schedule or browser etc Therefore if you are setting a schedule that is only for a particular day be sure to set your schedule in a way that will not impact on the next day s operation For example if you wish to p...

Страница 46: ...P CAHV group Note When setting a schedule for ventilator units the temperature setting is not displayed Moreover the prohibit remote controller operation is simply ON OFF Note Only the ON OFF operation is possible on the general equipment Air Conditioner Refer to 6 3 1 3 for the figure of LOSSNAY Air To Water PWFY general equipment and HWHP CAHV Date button Assign the schedule patterns to the date...

Страница 47: ...rent day schedule screen to bring up the schedule content setting screen Make the settings for the execution time and operation patterns ON OFF operation mode setting temperature airflow direction fan speed remote controller operation prohibition on the schedule content setting screen and then touch the OK button Not all settings need to be made The settings for only the operation mode or the sett...

Страница 48: ...dule to and touch Paste The settings of one type of equipment cannot be copied to the settings of a different type of equipment i e The settings of air conditioning units cannot be copied to ventilation equipment LOSSNAY settings Available operation modes and setting temperature range varies with models After all the settings have been made touch the OK button to save the schedule settings Touch t...

Страница 49: ...outdoor unit or system controller has not been registered in a group that is the object of the operation this area will be blank 3Unit address The address of the unit in error appears here If an Expansion controller EC is connected this field will appear in the EC No unit address format e g 1 012 4Number of malfunctioning units The number of malfunctioning units is displayed 5Error code The error ...

Страница 50: ... experiencing the problem DIDO controller PAC YG66DCA None Air To Water PWFY None HWHP CAHV None Units in error Units that stop AG 150A EC None Outdoor unit 51 Indoor unit 1 Indoor unit 2 Outdoor unit 53 Indoor unit 3 Indoor unit 4 Indoor unit 5 Outdoor unit 57 Air To Water PWFY 7 Indoor unit 1 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 3 Indoor unit 5 Indoor unit 4 Indoor unit 5 LOSSNA...

Страница 51: ...ar in the EC No unit address format e g 1 012 4Number of units withtriggered filter signs The number of units with currently triggered filter signs is displayed 5Reset units individually Touch Reset when you want to reset the filter sign for the group the units belong to Reset the filter sign after cleaning the filter 6All reset Touch All Reset when you want to reset the filter sign on all units w...

Страница 52: ...f when the error occurred is displayed 4Error source address The unit address of where the error occurred is displayed 5Error detection source address The unit address of where the error was detected is displayed 6Time Recovered The date and time of the error recovery is displayed 7Error code The error code of the error is displayed 8Clear log Touch Clear Log to clear the error log that is being d...

Страница 53: ... operations group name setting etc Note It is recommended to change the user name and password not to allow users other than the building manager to change the settings User Default user name Default password Available functions Maintenance User initial init All functions Building Manager administrator admin Out of all the functions the items to which access rights have been given are available To...

Страница 54: ... character capital button Touch to display the keyboard for entering Alphabetic characters capital 6Alphabetic character lower case button Touch to display the keyboard for entering Alphabetic characters lower case 7Numeric character symbol button Touch to display the keyboard for entering numeric characters and symbols 8OK button Touch to save the changes and return to the previous screen 9Cancel...

Страница 55: ...en is used it should not be sharp 2Clear button Clears the handwriting input area 3Input candidate character button Shows five candidate characters of high similarity with the input character Touch the button with a desired character to enter the character Note If a desired character is not shown press Clear button to clear the input area and rehandwrite slowly 4Memorized input word button Shows w...

Страница 56: ...ot use To unlock the screen enter the same username and password used to login The screen for both maintenance user and management user can be unlocked Screen lock button Touch If Use is selected the screen locks when the backlight is off after 10 minutes of not pressing anything Screen lock does not function when the Initial setting screen is open Screen lock button is shown on the Login screen T...

Страница 57: ...G 2000A Message that will appear when the clock has been reset If the power supply to the unit has been cut for an extended period due to power failure the clock will be reset and the following popup message will appear If this message appears set the clock from the Initial Settings screen The popup below will appear periodically until the clock setting is made If the unit is used without the cloc...

Страница 58: ...egistered number when Register the license is touched The Current Status is changed to Available If this fails check that the license number is entered correctly that the selection of the optional functions are made properly and that the time date settings on AG 150A is set correctly Consult your dealer for the availability of optional functions and for how to purchase the license for them Touch t...

Страница 59: ...button and enter the ID number for AG 150A in six numerical characters single byte or less Use this setting when you want to control multiple AG 150A units with unit IDs The unit ID that is entered here will be used on the display screen of the software that controls multiple AG 150A units and for the sender ID in the body of error messages 3 When connecting an Expansion controller press the EC co...

Страница 60: ...ough Hide Always show and Show during operation This setting is valid only on the AG 150A s LCD screen except the display of water temperature on the Air To Water PWFY unit 8 Press Save setting on the Unit info screen to save the setting 7 5 3 Adjusting the sound volume and screen brightness Sound volume and screen brightness are adjusted on this screen 1 Each touching of the sound volume control ...

Страница 61: ...G 150A dedicated LAN it is recommended to set the IP address as follows AG 150A Between 192 168 1 1 and 192 168 1 40 Web Monitor PC Between 192 168 1 101 and 192 168 1 150 2 Set the subnet mask Enter the subnet mask address for the AG 150A on the keyboard that appears when the subnet mask input button is touched Normally you should enter 255 255 255 0 3 When monitoring remotely or sending error ma...

Страница 62: ...ion is prohibited for both the remote control and subordinate system controllers or just for the remote control Touch SC RC when you want prohibited controllers to include both subordinate system controllers and the remote control or touch RC only when you only want to prohibit operation on the remote control Note Normally you should select SC RC 4 Press Save setting on the network screen to save ...

Страница 63: ...or each Expansion controller Check that the DB No of AG 150A itself and the DB No of the AG 150A on the Login screen match Note The Version is displayed after the IP addresses of Expansion controllers are set and the connections between AG 150A and the Expansion controllers are established 1 Setting up the Expansion controller IP address on the AG 150A 1 To set up the IP address of each EC first t...

Страница 64: ...etting determines the scope of this setting control i e operation is prohibited for both the remote control and subordinate system controllers or just for the remote control Touch SC RC when you want prohibited controllers to include both subordinate system controllers and the remote control or touch RC only when you only want to prohibit operation on the remote control Note Normally you should se...

Страница 65: ...ts in the group 1 To register air conditioning units select the unit selection button of the group to which the air conditioning units will be assigned Touch the model selection button on the screen that appears to display air conditioning units To register a ventilation device call up LOSSNAY to register Booster and Water HEX unit call up Air To Water PWFY and to register a Hot Water Heat Pump ca...

Страница 66: ...stem controllers are connected No remote controllers can be connected to a system to which four system controllers are connected The maximum connectable number is four including system controllers The remote controllers that are registered to another group will be grayed out and not available for selection 4 To register a system controller to a group touch the system controller selection button to...

Страница 67: ...ve the changes or touch the Cancel button to go back to the previous screen without saving any changes Note A maximum of 16 general equipment can be registered in one group Note To change the registered units to general equipment in the group in which air conditioners are registered disconnect the air conditioners first Note Only general equipments can be registered to the same group no air condit...

Страница 68: ... YG66DCA is counted as one unit Up to 50 units can be connected the controller for each EC connected Note Air conditioners and general equipment cannot be in the same group Note Remote controllers or system controllers cannot be connected to general equipment Note Devices that are connected to different Expansion controllers cannot be grouped together Refer to sections 7 7 1 P 64 7 7 2 P 64 and 7 ...

Страница 69: ...s from the TG 2000A so that the data in TG 2000A and AG 150A will match 1 To make the interlock setting for a LOSSNAY first touch the LOSSNAY button to bring up the LOSSNAY selection screen Touch the number assigned to the unit to be registered to select it An orange frame will appear around the selected items Touch again to deselect the selected items Touch again to deselect the selected item no ...

Страница 70: ...terlock settings for a system with connection to an Expansion controller PAC YG50ECA To interlock the ON OFF operation of the LOSSNAY units with the indoor units from the menu bar on the Setting change screen touch Initial Settings Interlock and open the LOSSNAY interlock settings screen Select the tab that corresponds to the EC controller whose settings are to be made and enter the interlock sett...

Страница 71: ...ck name button and enter the block name on the keyboard that appears in 20 characters or less Press Save setting on the block setting screen to save the settings Note The following characters cannot be used in the group name 7 9 2 Registering a group in a block Touch on the number of the group to register on the group selection screen that appears when the group button is touched An orange frame w...

Страница 72: ...s or less Press Save setting on the block setting screen to save the settings Note The following characters cannot be used in the group name 7 9 4 Registering groups in a block Touch the group button to display the group selection screen Select the tab that corresponds to the EC to which the groups are to be registered to Touch the numbers of the groups to be registered An orange frame will appear...

Страница 73: ...ting button Floor Name button Layout selection button Floor level button Select the total number of floors on the basic floor setting screen with the up down arrow buttons and select the desired type of floor layout Not all types of floor layouts may not be available depending on the number of floors No of floors 1 3 All floor layouts are selectable No of floors 4 5 1 row 1 column 2 1 1 2 3 1 2 2 ...

Страница 74: ... Floor File name Floor File name 1 floor_01 gif 6 floor_06 gif 2 floor_02 gif 7 floor_07 gif 3 floor_03 gif 8 floor_08 gif 4 floor_04 gif 9 floor_09 gif 5 floor_05 gif 10 floor_10 gif Floor layout Display range Floor layout Display range width 1 height 1 630 width 330 height width 1 height 2 630 width 660 height width 2 height 1 1260 width 330 height width 2 height 2 1260 width 660 height width 3 ...

Страница 75: ...six is not enough The followings are available colors for files RGB display Use only colors that are shown below otherwise the color may not be displayed correctly The initial setting of background color is RGB 103 103 103 To delete the set layout create a file that is painted with the initial background color and read it ...

Страница 76: ...cted group A pale orange frame will appear around the selected group With the pale orange frame being displayed select the floor to move the group to and touch the Paste button to move the selected group to the selected floor To cancel touch the Paste button with the cursor on the original group to deselect it and the orange frame will disappear Touch the Save Settings button to save the changes I...

Страница 77: ...d Press the group for one second then the frame of the icon turns from orange to yellow green and the icon becomes movable status Orange frame Press and hold for 1 second Yellow green frame movable status Drug drop to move Drug drop the icon under movable status to move anywhere within the group ...

Страница 78: ...YG50ECA To verify the information about the refrigerant systems that are connected to the AG 150A outdoor indoor unit connection information touch the Initial Settings System view from the menu bar on the Setting change screen On the System View screen select the tab that corresponds to the Expansion control whose refrigerant system connection information is to be verified In the System View scree...

Страница 79: ...ting multiple AG 150A to a system with connection to Expansion controllers P19 when doing so 2 Some settings may not be accessible if logged in as a building manager user Comparison between Master and Sub 1 To set the Time Master Sub setting to Master 2 Set the Time Master Sub setting to Sub Master Sub Clock setting Allowed Not allowed Clock synchronization Synchronized to the main controller Sync...

Страница 80: ...o the Expansion controllers Leave the factory setting Master 3 When high level system such as TG 2000A is connected to AG 150A Leave the factory setting Master Outdoor unit Indoor unit AG 150A PAC YG50ECA Master AG 150A Sub PAC YG50ECA PAC YG50ECA Master Outdoor unit Outdoor unit Indoor unit Indoor unit AG 150A Outdoor unit Indoor unit TG 2000A AG 150A AG 150A Outdoor unit Indoor unit Master Maste...

Страница 81: ... Available on the Advanced settings screen the Weekly schedule can be used If the Season setting is set to Not Available the Weekly schedule is not valid The factory setting is Available Leave the setting as it is Note When the license of Annual Weekly schedule is not registered the schedule season setting will not be displayed Season setting button ...

Страница 82: ...without a license To use the measurement data for energy saving peak cut control the energy saving peak cut license must be registered Make sure that required licenses have properly been registered on the window for registering the licenses for optional functions refer to section 7 4 If logged in as a building manager user certain functions may not be accessible When multiple AG 150A units are con...

Страница 83: ... the measurement settings window 8 1 2 Selecting meter types Select the type of controller to connect to each connected unit between AI controller PAC YG63MCA or PI controller PAC YG60MCA An orange frame will appear around the selected icon and the type of settable settings that appear on the right side of the window will change When AI controller is selected AI controller PI controller When PI co...

Страница 84: ...nsor name in 20 characters or less regardless of whether single byte or two byte characters are used The following symbols cannot be used for the sensor name and Sub menu Unit address 3 High Low alarm thresholds setting Correction value 4 Save Settings button Main menu 1 Enter Sensor name button 2 Sensor type selection button Current sensor reading Measurement range ...

Страница 85: ... settable range for the temperature sensor is between 100 0ºC 148 0ºF lower limit and 99 9ºC 211 9ºF upper limit The settable range for the humidity sensor is between 0 0 lower limit and 99 9 upper limit c Upper limit button Set the upper limit in the same manner d Correction value button Enter the correction value in the same manner as setting the lower limit value using the Correction value butt...

Страница 86: ...the OK button to save the settings and return to the measurement settings window b Enter the high alarm cancel value for H alarm OFF button Enter the value in the same manner as setting the H alarm ON c Enter the low alarm trigger value for L alarm ON button Enter the value in the same manner as setting the H alarm ON d Enter the low alarm cancel value for L alarm OFF button Enter the value in the...

Страница 87: ...ll may be left blank channels not used The default value is blank Note Be sure to set Pulse unit Numeric value Otherwise Pulse Unit Numeric Value or Pulse Unit Measurement Unit will not be saved 3 Setting the measurement unit Each pressing of the Pulse Unit Measurement Unit button next to Pulse unit will toggle through kWh m3 MJ blank kWh Select the unit that matches the value to be measured The d...

Страница 88: ...ter PWFY or general equipment Note When temperature are displayed in Fahrenheit 2 4 6 8 F may not properly be displayed because 1 2 3 4 C Control is excuted and then Celsius temperature is converted into Fahrenheit temperature inside the controller Outside air temperature Setting temperature after interlock Preset temperature 1 4 C 2 5 F or below Preset temperature Preset temperature 1 5 C 2 7 F P...

Страница 89: ...reset temperature for each air conditioning group For example when 4 C 8 F is selected and the preset temperature is 24 C 75 F the maximum set temperature will rise to 28 C 83 F along with outdoor temperature rise When 2 C 4 F is selected the maximum set temperature will rise to 26 C 79 F For groups that use outside temperature interlock function select 1 C 2 F 2 C 4 F 3 C 6 F 4 C 8 F button depen...

Страница 90: ...s screen select the tab that corresponds to the Expansion controller that is connected to the desired group and make the control level settings for each group Note If the user logs in as a building manager some of the operations may be prohibited Note When multiple AG 150A controllers are connected by connecting an Expansion controller to the system this function should only be used on one of the ...

Страница 91: ... night setback function the time period of this control has to be set Touch Setback control time period setting button then Setback control screen appears as shown below Lower limit temperature 12 C 53 F Setback operation stops when the temperature rises 3 C 5 4 F or the control time period is over Setback operation starts Upper limit temperature 28 C 83 F Setback operation starts When the tempera...

Страница 92: ...back control will not be operated After setting press OK to reflect the setting Setback setting screen will be shown If the temperature is not changed touch Cancel Note The setting lower limit temperature upper limit temperature Note The settable temperature varies depending on the model Note When CITY MULTI S Series PUMY is used set the temperature at 17 C 63 F or above in heating mode After setb...

Страница 93: ... settings are to be changed and then set the upper and lower temperature limits Note If the user logs in as a building manager some of the operations may be prohibited Note Be sure to make the settings while the Expansion controller is connected Note When multiple AG 150A controllers are connected by connecting an Expansion controller to the system this function should only be used on one of the A...

Страница 94: ... that appears in 20 characters or less 2 Changing the password To change the maintenance user password touch the password input button and enter the password that is between 3 and 10 character long on the keyboard that appears Press Retype Password and enter the same password again On the screen password will appear as asterisks with each representing a character Press the Save setting button to r...

Страница 95: ...utton and enter the password that is between 3 and 10 character long on the keyboard that appears Press Retype Password and enter the same password again On the screen password will appear as asterisks with each representing a character Press the Save setting button to reflect the new user name and password The same user name and password are used to log in to Web browser 3 Making the settings for...

Страница 96: ... outside temperature interlock function Setback Setting of setback function Note The table below shows USB memory devices that have been confirmed to work As of February 2012 Asterisks in the Model column describe colors Do not make a security function setting when using No 10 12 13 or 14 If any USB memory above cannot be obtained use a memory device that meets the following three conditions Test ...

Страница 97: ...d The data can be copied only when logged in as a maintenance user 3All settings Touch the button to select and touch again to deselect When this button is selected the Initial Settings and User Info buttons are deselected When the Initial Settings or User Info button is selected this button is deselected With the button selected touch the Copy to USB Memory button to copy all the AG 150A setting ...

Страница 98: ... from USB Memory button to read the AG 150A user information from the SetupData folder of the USB memory 3All settings Touch the button to select and touch again to deselect When this button is selected the Initial Settings and User Info buttons are deselected When the Initial Settings or User Info button is selected this button is deselected With the button selected touch the Read from USB Memory...

Страница 99: ...Setback Web browser Initial Settings Basic System Web browser Initial Settings Groups Web browser Initial Settings Interlocked LOSSNAY Web browser Initial Settings Blocks Web browser Functions 1 E Mail Web browser Functions 1 Peak Cut Web browser Functions 1 Measurement Web browser Functions 2 Set Temperature Range Limit Web browser Functions 2 Night Mode Schedule Web browser Functions 2 System ch...

Страница 100: ...gs button to import the setting data Copying the data to a USB memory Data A Data A AG 150A setting data for Day 1 Reading the data Data AA Data A AG 150A setting data for Day 2 Data BB Data A Data BB AG 150A setting data after the data is imported Data AA will be overwritten by the data in the USB memory Data A Data BB will remain as it is Reading the data Data AA Data A AG 150A setting data for ...

Страница 101: ...of the USB memory in a CSV format If the folder does not already exist one will be created The date folder will be created in the format that was specified on the Unit Info screen This item cannot be selected unless Charge License has been registered 3Output as CSV file With the Charge parameters or Power consumption data button selected touch this button to output the selected data to the USB mem...

Страница 102: ... 1 is settable File contents The format of each CSV file is as follows Each file contains up to 62 days of data Delimiter or and decimal point or that are used by the CSV file are selected on the Initial Setting Web Charge parameter data range is 0 through 999999 If the count value exceeds the maximum value the count value goes back to 0 The file is not output until the operation starts because th...

Страница 103: ...an Expansion controller number 1 3 address two digits and Time zone one digit Power consumption data range is 0 00 through 999999 99 If the count value exceeds the maximum value the count value goes back to 0 00 The file is not output until the operation starts because the data does not exist When the Energy Management License Pack or Charge License has not been registered the file is not output C...

Страница 104: ...ft top center top right top left middle center right middle left bottom center bottom and right bottom Every time the square is touched the next square will appear When all nine squares are touched calibration is complete and the display will return to the touch panel calibration screen If the screen is left untouched for one minute the display will automatically return to the calibration screen a...

Страница 105: ...r one with Ethanol when cleaning Do not use any organic solvent acid or alkali solution Item Description Number Pressing the buttons 1 through 4 in the ascending order will take the screen back to the original screen main operation screen To go back to the previous screen these buttons must be touched in the correct order starting with button 1 Touching the buttons in the wrong order will cancel a...

Страница 106: ... Do not use Perform emergency stop with level signal Emergency Stop Level signal During emergency stop only ON OFF of the centralized controller and local remote controller operation will be prohibited Scheduled operations cannot be performed Perform ON OFF operation with level signal ON OFF Level signal Only the ON OFF operation of the centralized controller and the local remote controller will b...

Страница 107: ...nals While the Emergency stop contact is ON centralized controller and local remote controller operation ON OFF only is prohibited After the emergency stop is cancelled air conditioning systems will remain stopped and will require manual operation if they need to be started back up When level signals are used for ON OFF centralized controller and local remote controller operation ON OFF only is pr...

Страница 108: ...in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which...

Страница 109: ...e abnormality 63L trip A 1503 Ref cycle not operate due to coil frost 1504 Ref cycle not operate due to overheat protection 1505 Ref cycle not operate due to compressor vacuum operation protection refrigerant low temperature abnormality 1506 Ref cycle not operate due to refrigerant pump abnormality 1507 Ref cycle not operate due to composition detection abnormality 1508 Ref cycle not operate due t...

Страница 110: ...ric system not operate due to electric leak 4105 Electric system not operate due to short circuit 4106 Electric system not operate due to self power supply OFF power failure 4107 Electric system not operate due to overlord 4108 Electric system not operate due to overlord protection OCR51C Open phase S phase Open connector 51CM A 4109 Electric system not operate due to OCR51F 4110 Electric system n...

Страница 111: ...nsor trouble Sensor No 5300 Current sensor abnormality A 53 Current sensor trouble Sensor No 54 Humidity sensor trouble Sensor No 55 Gas sensor trouble Sensor No 56 Air speed sensor trouble Sensor No 57 Limit switch trouble Switch No 58 Sensor trouble Sensor No 59 Other sensors trouble Sensor No 6000 System abnormality 6101 System not operate due to abnormality With response frame 6102 No answer b...

Страница 112: ...rs 6821 Other communication errors Transmission line busy 6822 Other communication errors No communication ACK 6823 Other communication errors No response command 6824 Other communication errors Receive data error 6830 Communication error MA communication refrigerant address double setting error 6831 Communication error No MA communication reception error 6832 Communication error MA communication ...

Страница 113: ...del error 7131 System abnormality Mixed cooling only H P connection error Facility PAC 7132 System abnormality Multiple entries of operation performance Facility PAC 7200 System abnormality Numeric values unsettled 7201 System abnormality Numeric values unsettled 73 System abnormality LON system equipment abnormality 6920 No response error 6922 Response ID error 7901 Maximum connectable No of unit...

Страница 114: ...ection 6 4 X14 New Function Group Schedule Available Not Available An item Schedule Available Not Available has been added to the explanations of the group control screen Notes have been added about Schedule Available Not Available function P3 P19 P23 P26 P29 P35 P41 P44 P46 Section 3 Section 5 3 Section 6 Section 6 1 Section 6 2 Section 6 3 1 Section 6 3 2 1 Section 6 3 2 2 Section 6 3 2 3 Modifi...

Страница 115: ...ion 5 3 Section 6 Section 6 1 Section 6 2 Section 6 3 1 Section 6 3 2 1 Section 6 4 Section 7 7 Section 7 9 2 Section 7 11 New Function Measurement settings Measurement settings were added Temperature sensor and humidity sensor settings with connection to an AI controller Watt hour meter settings with connection to a PI controller P3 P6 P24 P26 P81 P94 P98 Section 3 Section 4 Section 6 Section 6 1...

Страница 116: ...e number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC WT05369X15 ...

Отзывы: