– 64 –
7-7 Group Setting
Touch the [Groups] tab in the screen that appears when [Initial Settings] on the menu bar in the setting change screen is touched to open the
group setting screen and set and register the group names for the air conditioning units or general equipment to be connected to AG-150A.
Note: If the user logs in as a building manager, some of the operations may be prohibited.
Note: If the system is connected to the TG-2000A, make all settings and changes from the TG-2000A so that the data in TG-2000A and
AG-150A will match.
Note: A contact on the genera interface device is regarded as one unit. The number of units that can be connected to AG-150A is up to 50.
Note: Different models cannot be in the same group.
Note: Remote controllers or system controllers cannot be connected to general equipment.
Note: Each contact point on the general equipment is counted as one unit.
7-7-1
Setting the Group Name
Press the Group name input button, and enter the group name on the keyboard that appears in 20 characters or less.
Note: The following characters cannot be used in the group name: < > & " '
7-7-2
Registering air conditioner units in the group
(1) To register air conditioning units, select the unit selection button of the group to which the air conditioning units will be assigned.
Touch the model selection button on the screen that appears to display air conditioning units. (To register a ventilation device call up
“LOSSNAY,” to register Booster and Water HEX unit call up “Air To Water (PWFY),” and to register a Hot Water Heat Pump call up
“HWHP (CAHV)” on the screen.) Then touch the numbers that are assigned to the units to register. An orange frame will appear
around the units that are selected.
Touch again to deselect the selected item (no orange frame).
Press the [OK] button to save the changes, or touch the [Cancel] button to go back to the previous screen without saving any
changes.
Note: A maximum of 16 air conditioner units can be registered in one group.
Note: To change the registered units to air-conditioners in the group in which general equipment is registered, disconnect the
general equipment first.
Note: Only the same type of equipment (e.g., only the air conditioning units) can be registered to each group.
Group No.
Group numbers
will be displayed
here.
Group Name
Input button
Unit selection
button
Remote controller
selection button
System controller
selection button
Save Setting
button
Icon selection
button
Model selection
button
Unit selection
button
WT05369X15.book Page 64 Wednesday, November 7, 2012 10:33 AM