– 29 –
6-2 Operation setting/Prohibition setting from local remote controller
The setting for the control of air conditioning units (LOSSNAY, general equipments, Air To Water (PWFY)) and the permit/prohibit setting
from the local remote controller are made on this screen.
* The screen will show the status of the units at the time the screen is opened, any change that may take place after the screen is
opened will not be reflected.
* The changes made on the screen will not be reflected until the OK button is pressed.
(1) Air conditioning unit group
Function
Operation method
Display
1
ON/OFF
Select the operation
status (ON or OFF).
An orange frame will appear around the selected button.
2
MODE
Select the desired
operation mode from
one of the icons below
“Mode”.
An orange frame will appear around the selected mode.
* If an attempt is made to change the mode setting for the groups for which the
operation prohibition setting is enabled, the changes will not be reflected and a pale
orange frame will appear around the group.
3
Set Temperature Set the temperature by
using the Up/Down
arrows below “Set
Temp” function.
Pressing the Up/Down arrow increases/decreases the temperature by one degree
respectively.
The settable temperature range depends on the mode and model. If the Up arrow is
pressed when the upper limit temperature is displayed. the lower limit temperature will
appear, and the Down arrow vice versa.
(Depending on the model details, the temperature range may change and Auto
setting may not be available.)
*If operation modes and preset temperature are changed from multiple controllers
(e.g., system controller and remote controller) almost simultaneously, the preset
temperature that appears on the display may be outside the settable temperature
range.
*1 This model includes DEDICATED OUTSIDE AIR SYSTEM (DOAS).
3
Temperature
6
Remote controller
operation prohibit switch
7
Schedule
Available/Not Available
a
OK
b
Cancel
4
Air Direction
5
Fan Speed
0
Fan speed of
interlocked unit
9
Operation status
of interlocked unit
1
ON/OFF switch
2
Operation mode switch
Item selection
frame
An orange frame
appears around
the selected item.
8
Filter sign reset
Model
Cooling/Dry
Heating
Auto
Standard temp
model
19 ~ 30°C
[67 ~ 87°F]
17 ~ 28°C
[63 ~ 83°F]
19 ~ 28°C
[67 ~ 83°F]
Mid temp model
(CITY MULTI)
14 ~ 30°C
[57 ~ 87°F]
17 ~ 28°C
[63 ~ 83°F]
17 ~ 28°C
[63 ~ 83°F]
Mid temp model
(Mr. Slim)
(M-series)
(P-series)
14 ~ 30°C
[57 ~ 87°F]
14 ~ 28°C
[57 ~ 83°F]
14 ~ 28°C
[57 ~ 83°F]
Low temp model
*1
8 ~ 30°C
[46 ~ 87°F]
8 ~ 28°C
[46 ~ 83°F]
8 ~ 28°C
[46 ~ 83°F]
WT05369X15.book Page 29 Wednesday, November 7, 2012 10:33 AM