Using the Configurator
157
Line
Attached Fire Alarm
Report Priority
Timers
Dial Using
Select
Tone
or
Pulse
.
Wait for dial tone before
dialing
Select this check box if you want the dialer to wait for a
dial tone before dialing.
Communication Protocol
Level 0, Level 1, Level 2 or Level 1G. Only Level 2
(FX2000) is appropriate.
Checksum
8 Bit / 16 Bit. For FX2000 16 bit is appropriate.
Event
Specifies whether the internal Ckt No or a combination of
Loop and Address is sent to the monitoring station.
Output
0-9999. This value is added to outputs to differentiate
them from inputs with the same Ckt No.
Alarm
Select the account that will report alarms.
Supervisory
Select the account that will report supervisory alerts.
Trouble
Select the account that will report trouble alerts.
AC loss delay
If there is a loss of AC power, the dialer waits this amount
of time before calling the monitoring station.
Line 2 cellular test
If this check box is unselected, then there is no test
reporting for a cell phone, or the phone line is a regular
line. Select this check box to set the test report date for
the cell phone setup. Set the
Day of month
from 01 to 28
to schedule a test for Line 2 on a certain day of the month.
See section 19.11.1 on page 159 for more information.
When a cell phone service is employed for the panel, it
should only be connected to telephone line #2 CO
interface. Also, the dial tone detection feature of Line 2
should be disabled for cell phone application.