background image

Copyright 2005 Wheelock, Inc.  All rights reserved. 

 

 

 

 

 

  

P83884 J 

 

 

        Sheet 1 of 4 

 

273 Branchport Ave. 
Long 

Branch, 

N.J. 

 

07740        

Thank you for using our products.

 

(800)  631-2148 
www.wheelockinc.com                                  INSTALLATION INSTRUCTIONS 

SERIES RSSR STROBE APPLIANCES 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 

Wheelock’s Series RSSR Strobes can provide a non-synchronized strobe appliance when connected directly to a fire alarm control panel (FACP), or provide a 
synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s PS-12/24-8 Power Supply with 
patented sync protocol.  The RSSR Strobe appliances are UL Listed under Standard 1638 for Emergency Devices.  The RSSR-2415C, RSSR-2475C and RSSR-
24110C strobes are intended for 

ceiling mount only

 and the RSSR-2415W, RSSR-2475W and RSSR-24110W strobes are intended for 

wall mount

 

only,

 with the 

backboxes specified in these instructions (See Mounting Options).  The RSSR models have an integrated strobe mounting plate (SMP) that can be mounted to a 
single-gang, double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox.  The strobe uses a xenon flashtube with solid state circuitry 
enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling.  All inputs are polarized for compatibility with 
standard reverse polarity supervision of circuit wiring by an FACP. 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF 
THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR 
DEATH TO YOU AND/OR OTHERS. 

 

SPECIFICATIONS: 

Table 1:  UL Models and Ratings 

Model 

 

Regulated 

Voltage 

(VDC/VRMS) 

Voltage  

Range 

(VDC/VRMS) 

Strobe Candela  

(cd) 

Mounting 

Options 

RSSR-2415C 24 

16.0-33.0 

 

15 

A,B,C,D 

RSSR-2415W 24 

16.0-33.0 

 

15 

A,B,C,D 

RSSR-2475C 24 

16.0-33.0 

 

75 

A,B,C,D 

RSSR-2475W 24 

16.0-33.0 

 

75 

A,B,C,D 

RSSR-24110C 24 

16.0-33.0 

110 

A,B,C,D 

RSSR-24110W 24 16.0-33.0 

110 

A,B,C,D 

NOTES: 

1.

 

Strobes will produce 1 flash per second over the “Regulated Voltage” range. 

2.

 

All models are for indoor use with a temperature range of +32

°

F  to +120

°

F  (0

°

C to +49

°

C) and maximum humidity of 85% RH.  The effect of shipping 

and storage temperatures shall not adversely affect the performance of the appliance when  it is stored in the original cartons and is not subjected to misuse 
or abuse.   

 

A7

A4

A6

A1

A5

A3

A2

 
 

Table 2:  Candela at Various Angles Per UL 1638 

Model Rated 

Candela 

 
   A1     A2    A3          A4     A5      A6/A7 

RSSR-2415C 

  15.0cd 

      15         1.3        1.3         1.2        1.2          0.7 

RSSR-2415W 

  15.0cd 

      15         1.3        1.3         1.2        1.2          0.7 

RSSR-2475C 

  75.0cd 

      75         6.7        6.7         6.2        6.2          3.3 

RSSR-2475W 

  75.0cd 

      75         6.7        6.7         6.2        6.2          3.3 

RSSR-24110C 

110.0cd 

    110         9.8        9.8         9.1        9.1          4.8 

RSSR-24110W 

110.0cd 

    110         9.8        9.8         9.1        9.1          4.8 

 

When calculating the total currents use Table 3 to determine the highest value of RMS current for an individual strobe, then multiply these values by the total number of 
strobes.  Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety 
factors. 

NOTE:  

The maximum number of strobes on a single notification appliance circuit shall not exceed 50. 

  

 

Table 3:  UL Current Ratings (AMPS) 

Maximum RMS Current Draw 

UL Voltage 

2415C/W 

2475C/W 

24110C/W 

DC 

  16-33VDC 

0.090 

0.315 

0.420 

FWR  

16-33VRMS 

0.145 

0.480 

0.645 

CAUTION:  

These notification appliances are UL Listed as “Regulated”.  They are intended to be used with FACPs whose notification circuits are UL Listed as 

“Regulated.”  These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the 
installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual. 

 

WARNING:  THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING 

FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE.  DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.  

 

 

Содержание RSSR-2415C

Страница 1: ...SSR 2415W 24 16 0 33 0 15 A B C D RSSR 2475C 24 16 0 33 0 75 A B C D RSSR 2475W 24 16 0 33 0 75 A B C D RSSR 24110C 24 16 0 33 0 110 A B C D RSSR 24110W 24 16 0 33 0 110 A B C D NOTES 1 Strobes will produce 1 flash per second over the Regulated Voltage range 2 All models are for indoor use with a temperature range of 32 F to 120 F 0 C to 49 C and maximum humidity of 85 RH The effect of shipping an...

Страница 2: ...limits are exceeded there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product CAUTION Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit especially if sheathed multiconductor cable or 3 4 conduit fittings are used Although the limits shown for each mountin...

Страница 3: ...N SEVERE ELECTRIC SHOCK WARNING WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS WITH THE INTENSITY NUMBER AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUM...

Страница 4: ...ATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIREMENTS WH...

Отзывы: