7.2.7 Setting of the instrument parameters
Electronic Setting of the instrument parameters
Setting of the instrument parameters with the user program
With the control 09 (ST09) the parameters are assigned over the soft-
ware in Mode IS of the "user program part"
Units with serial numbers >OT1.02000 or retrofitted units
Adjustment with the keys on the main CPU located under foot part of
the unit.
- press „Set Up“
- with „
“ click on Modus IS
- Press „Enter“
- Press „
“ to the number of the instrument to
be changed
- press „Enter“
- chose the level with „
or
“
X
_
lower instrument parameter in level X
X
_
upper instrument parameter in level X
Caution:
With the 5-function pedal control only the X
_
instrument parameter is used.
- press "Enter"
- with „
or
“ individually click the required
…% parameters
For the factory settings see instrument
descriptions 7.7 to 7.11
- press "Enter" for 1.5 seconds
- "i.O." is displayed
parameter is saved
- press "Setup" to return to the level selection
Next level can be chosen
- After correction/setting of all the required levels
the user program can be left by pressing
3 x "Setup".
Caution!
The functions „CF“, „CI“, „Cd“, „FS“, „FC“ and „CL“ are service func-
tions. They may only be changed by trained staff.
Individual basic
adjustment of the
instruments data
The chosen
speed is saved
TA
1
TA
2
TA
3
TA
4
SETUP
ENTER
S
et
up
S
et
up
Cu
DN
Cu
UP
O P
U P
Cu
DN
C
u
U
P
C
u
U
P
Cu
D
N
S
et
up
SP
Cu
DN
Cu
UP
I N
I S
ENTER
Cu
D
N
Cu
D
N
00......99 %
ENTER
Cu
DN
Cu
UP
- +
ENTER
>1,5
Sek
i.O.
ENTER
1 _
1
_
2 _
2
_
3 _
3
_
4 _
4
_
1 _
1
_
2 _
2
_
3 _
3
_
4 _
4
_
Setup
1.
2.
3.
4.
5.
6.
1. H
2. H
3. H
4 .H
5. H
6. H
1. C
2. C
3. C
4. C
5. C
6. C
!One step back always with SETUP!
Micromotor 1
Micromotor 2
Ultrasonic
Turbine 1
Turbine 2
...............
Micromotor 1
Micromotor 2
Ultrasonic
Turbine 1
Turbine 2
..............
Micromotor 1
Micromotor 2
Ultrasonic
Turbine 1
Turbine 2
.............
Instruments data
Level 1
Instruments data
Level 2
Instruments data
Level 3
Instruments data
Level 4
The instrument parameters can be set individually per instrument
within the 4 levels.
With the control 01 (ST01) the four speed/intensity levels are adjusted
with the potentiometers on the electronic boards.
Units with serial numbers <OT1.01999
MM1
Micromotor 1
MM2
Micromotor 2
TU1
Turbine 1
TU2
Turbine 2
UL
Ultrasonic device
Rotating direction
increase of the speed- / intensity level
Rotating direction
decrease of the speed- / intensity level
For the factory settings see instrument descriptions 7.7 to 7.11
MM1
MM2
TU1
TU2
UL
Enlarged programming instructions see page 21