8.4.5 Drying mode
For MSX-07HRN1-QC2, MSX-09HRN1-QC2,
MSX-12HRN1-QC2,
MSX-18HRN1-QC2 models:
8.4.5.1 The indoor fan will run following the compressor. If the compressor is on ,the indoor fan will run
at low speed. If the compressor is off, the indoor fan will run at breeze.
Running rules:
No
Condition
Indoor fan
Compressor and outdoor fan
1
T1
≥
TS+2
Low
Breeze
ON 6 minutes
OFF 4 minutes
2
TS
≤
T1
<
TS+2
Low
Breeze
ON 5 minutes
OFF 5 minutes
3
T1
<
TS
Low
Breeze
ON 4 minutes
OFF 6 minutes
8.4.5.2 In drying mode, if room temperature is lower than 10
, the
℃
indoor fan will run at breeze while
the compressor and outdoor fan will stop and not resume until room temperature exceeds 13
.
℃
8.4.5.3 System protection is active in this mode.
For MSX-21HRN1-QB8W, MSX-24HRN1-QB8W
models:
8.4.5.4 The indoor fan will keep running at low speed.
8.4.5.5 The outdoor fan, compressor and all the protections are the same with cooling mode.
8.4.6 Forced operation function
Press the touch button continually, the AC will run as below sequence:
Forced auto
→
Forced cooling
→
Off
Forced cooling mode:
The compressor and outdoor fan keep running and the indoor fan runs at low speed. After running for
30 minutes, AC will turn to auto mode with 24
℃
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as normal auto mode with 24
℃
setting temperature.
l
When AC receives signals, such as switch on, switch off, timer on, timer off, mode setting ,fan
speed setting ,sleeping mode setting ,follow me setting, it will quit the forced operation.
Содержание MOA-07HN1-QC2
Страница 1: ...XSEU A 1202 SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET SPLIT WALL MOUNTED TYPE X ON OFF SERIES...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units MSX 07HRN1 QC2 MSX 09HRN1 QC2 MSX 12HRN1 QC2 MSX 18HRN1 QC2...
Страница 16: ...14 MSX 21HRN1 QB8W MSX 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units MOA 07HN1 QC2...
Страница 18: ...16 MOA1 09HN1 QC2 MOA 09HN1 QC2 MOB1 12HN1 QC2 MOB 12HN1 QC2...
Страница 19: ...17 MOF 18HN1 QC2...
Страница 20: ...18 MOF1 21HN1 QB8W MOF3 24HN1 QB8W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 35: ...33 Ionizer Plasma function indicator This indicator illuminates when Ionizer Plasma function is on...