34
8.3 Main Protection
8.3.1 Time Delay at restart for compressor.
8.3.2 Fan Speed is out of control. (only for MSX-07HRN1-QC2, MSX-09HRN1-QC2,
MSX-12HRN1-QC2,
MSX-18HRN1-QC2 models)
----When Indoor Fan Speed keeps too low or too high for certain time, the unit will stop and the LED
will display the failure
8.3.3 Current protection
I3SEC
I5MIN
A
B
C
Resume
IFAN
IRESTORE
A zone : The current exceeds I
3SEC
for 5 seconds, the compressor and outdoor fan will shut off.
B zone: The current exceeds I
5min
for 5 minutes, the compressor and outdoor fan will shut off.
C zone: The current exceeds I
FAN
, the outdoor fan will shut off if AC is in heating mode. If AC is in
cooling mode, the indoor fan will run at low speed.
I
3SEC
=7.0A, I
5min
=6.0A, I
FAN
=5.0A, I
RESTORE
=6.5A for MSX-07HRN1-QC2 model.
I
3SEC
=10.0A, I
5min
=7.5A, I
FAN
=6.0A, I
RESTORE
=5.0A for MSX-09HRN1-QC2 model.
I
3SEC
=12.0A, I
5min
=8.5A, I
FAN
=7.5A, I
RESTORE
=6.5A for MSX-12HRN1-QC2 model.
I
3SEC
=19.5A, I
5min
=17.0A, I
FAN
=15.0A, I
RESTORE
=13.0A for MSX-18HRN1-QC2 model.
I
3SEC
=22.0A, I
5min
=20.0A, I
FAN
=16.0A, I
RESTORE
=14.0A for MSX-21HRN1-QB8W model.
I
3SEC
=26.0A, I
5min
=24.0A, I
FAN
=19.0A, I
RESTORE
=17.0A for MSX-24HRN1-QB8W model.
8.3.4 Zero crossing detection error protection (only for MSX-07HRN1-QC2, MSX-09HRN1-QC2,
MSX-12HRN1-QC2,
MSX-18HRN1-QC2 models)
If AC can not detect zero crossing signal for 4 minutes or the zero crossing signal time interval is not
correct, the unit will stop and the LED will display the failure. The correct zero crossing signal time
interval should be between 6-13ms.
Содержание MOA-07HN1-QC2
Страница 1: ...XSEU A 1202 SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET SPLIT WALL MOUNTED TYPE X ON OFF SERIES...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units MSX 07HRN1 QC2 MSX 09HRN1 QC2 MSX 12HRN1 QC2 MSX 18HRN1 QC2...
Страница 16: ...14 MSX 21HRN1 QB8W MSX 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units MOA 07HN1 QC2...
Страница 18: ...16 MOA1 09HN1 QC2 MOA 09HN1 QC2 MOB1 12HN1 QC2 MOB 12HN1 QC2...
Страница 19: ...17 MOF 18HN1 QC2...
Страница 20: ...18 MOF1 21HN1 QB8W MOF3 24HN1 QB8W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 35: ...33 Ionizer Plasma function indicator This indicator illuminates when Ionizer Plasma function is on...