38
8.4.2.5
Condenser
high
temperature
T3
protection.(only
for
MSX-21HRN1-QB8W,
MSX-24HRN1-QB8W model)
T3
TE10
Off
On
TE11
When T3
≥
TE10, the compressor will shut off. When T3
<
TE11,the compressor will restart.
TE10=65
℃
, TE11=55
℃
.
8.4.3 Heating Mode
8.4.3.1 Compressor running rules:
Every time, the compressors start up, they will keep running for
△
t minutes (protections are active)
and then follow the below rules. (While
△
t=7.)
When indoor room temp.T1 is higher than Tj, the compressor and outdoor fan will shut off. When T1 is
lower than Tk, the compressor and outdoor fan will start up.
Tj=Ts+6
Tk=Ts+4. for MSX-07HRN1-QC2, MSX-09HRN1-QC2,
MSX-12HRN1-QC2,
MSX-18HRN1-QC2
models.
Tj=Ts+3
Tk=Ts+2.for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models.
8.4.3.2 Outdoor fan running rules:
The outdoor units have single fan speed. The outdoor fan will run following the compressor except
when AC is in evaporator high temp. protection in heating mode , condenser high temp. protection in
Содержание MOA-07HN1-QC2
Страница 1: ...XSEU A 1202 SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET SPLIT WALL MOUNTED TYPE X ON OFF SERIES...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units MSX 07HRN1 QC2 MSX 09HRN1 QC2 MSX 12HRN1 QC2 MSX 18HRN1 QC2...
Страница 16: ...14 MSX 21HRN1 QB8W MSX 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units MOA 07HN1 QC2...
Страница 18: ...16 MOA1 09HN1 QC2 MOA 09HN1 QC2 MOB1 12HN1 QC2 MOB 12HN1 QC2...
Страница 19: ...17 MOF 18HN1 QC2...
Страница 20: ...18 MOF1 21HN1 QB8W MOF3 24HN1 QB8W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 35: ...33 Ionizer Plasma function indicator This indicator illuminates when Ionizer Plasma function is on...