25
from the 3-way valve
’
s service port immediately and turn off the air conditioner before disconnecting the
hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
6.5 Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make
the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
Electronic scale
Содержание MOA-07HN1-QC2
Страница 1: ...XSEU A 1202 SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET SPLIT WALL MOUNTED TYPE X ON OFF SERIES...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units MSX 07HRN1 QC2 MSX 09HRN1 QC2 MSX 12HRN1 QC2 MSX 18HRN1 QC2...
Страница 16: ...14 MSX 21HRN1 QB8W MSX 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units MOA 07HN1 QC2...
Страница 18: ...16 MOA1 09HN1 QC2 MOA 09HN1 QC2 MOB1 12HN1 QC2 MOB 12HN1 QC2...
Страница 19: ...17 MOF 18HN1 QC2...
Страница 20: ...18 MOF1 21HN1 QB8W MOF3 24HN1 QB8W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 35: ...33 Ionizer Plasma function indicator This indicator illuminates when Ionizer Plasma function is on...