40
When T1-Ts>2
℃
,the indoor fan will run at low speed.
When T1-Ts
≤
0
℃
, the indoor fan will run at medium speed.
8.4.3.4 Defrosting mode
:
For MSX-07HRN1-QC2,MSX-09HRN1-QC2,
MSX-12HRN1-QC2,
MSX-18HRN1-QC2 models:
l
Condition of defrosting:
AC will enter defrosting mode if any of the following items
①
&
②
is satisfied
:
①
AC meets A+B1 or A+B2.
A: The cumulative compressor running time is over 42 minutes.
B1: The cumulative compressor running time is between 42~120 minutes. Meanwhile the T2-T1 meet
the below table.
℃
T2
-
T1
High speed
<
TH
DEFROST
Medium speed
<
TM
DEFROST
Low speed
<
TL
DEFROST
Breeze/off
No need to compare the T2 and T1
B2: The cumulative compressor running time is over 120 minutes. Meanwhile the T2-T1 meet the
below table.
℃
T2
-
T1
High speed
<
TH
DEFROST
+2
Medium speed
<
TM
DEFROST
+2
Low speed
<
TL
DEFROST
+2
Breeze/off
No need to compare the T2 and T1
②
After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2
protection cumulates up to 90 minutes.
While TH
DEFROST
=14
℃
,
TM
DEFROST
=16
℃
, TL
DEFROST
=17
℃
for MSX-07HRN1-QC2 model.
TH
DEFROST
=15
℃
,
TM
DEFROST
=17
℃
, TL
DEFROST
=19
℃
for MSX-09HRN1-QC2 model.
TH
DEFROST
=14
℃
,
TM
DEFROST
=15
℃
, TL
DEFROST
=16
℃
for MSX-12HRN1-QC2 model.
TH
DEFROST
=17
℃
,
TM
DEFROST
=18
℃
, TL
DEFROST
=19
℃
for MSX-18HRN1-QC2 model.
l
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to
normal heating mode.
Содержание MOA-07HN1-QC2
Страница 1: ...XSEU A 1202 SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET SPLIT WALL MOUNTED TYPE X ON OFF SERIES...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units MSX 07HRN1 QC2 MSX 09HRN1 QC2 MSX 12HRN1 QC2 MSX 18HRN1 QC2...
Страница 16: ...14 MSX 21HRN1 QB8W MSX 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units MOA 07HN1 QC2...
Страница 18: ...16 MOA1 09HN1 QC2 MOA 09HN1 QC2 MOB1 12HN1 QC2 MOB 12HN1 QC2...
Страница 19: ...17 MOF 18HN1 QC2...
Страница 20: ...18 MOF1 21HN1 QB8W MOF3 24HN1 QB8W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 35: ...33 Ionizer Plasma function indicator This indicator illuminates when Ionizer Plasma function is on...