AC will enter defrosting mode if any of the following items is satisfied.
(1) When T3
<
TC1
, if the
℃
compressor keeps running over 45 minutes and T3
<
TC3
for 3
℃
minutes. While TC1= 0
,
℃
TC3=
-
3
.
℃
(2) After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2
protection cumulates up to 90 minutes.
l
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to
normal heating mode.
(1) T3 rises to be higher than TC2. TC2= 20
℃
.
(2) The machine has run for 10 minutes in defrosting.
l
Defrosting action
:
8.4.3.5 High evaporator coil temp.T2 protection:
For MSX-07HRN1-QC2 model, MSX-09HRN1-QC2,
MSX-12HRN1-QC2,
MSX-18HRN1-QC2
models:
While TE7=63
℃
,TE8=53
℃
,TE9=51
℃
for MSX-07HRN1-QC2 model
Содержание MOA-07HN1-QC2
Страница 1: ...XSEU A 1202 SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET SPLIT WALL MOUNTED TYPE X ON OFF SERIES...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units MSX 07HRN1 QC2 MSX 09HRN1 QC2 MSX 12HRN1 QC2 MSX 18HRN1 QC2...
Страница 16: ...14 MSX 21HRN1 QB8W MSX 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units MOA 07HN1 QC2...
Страница 18: ...16 MOA1 09HN1 QC2 MOA 09HN1 QC2 MOB1 12HN1 QC2 MOB 12HN1 QC2...
Страница 19: ...17 MOF 18HN1 QC2...
Страница 20: ...18 MOF1 21HN1 QB8W MOF3 24HN1 QB8W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 35: ...33 Ionizer Plasma function indicator This indicator illuminates when Ionizer Plasma function is on...