protection in cooling mode, defrosting mode and the current protection.
8.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and
auto.
The auto fan:
8.4.2.4 Evaporator low temperature T2 protection.
When the evaporator coil temp.T2 keeps lower than TE5 for 5 minutes, the compressor and outdoor
fan will shut off.
When T2 is higher than TE6, the compressor and outdoor fan will restart up.
While TE5=4
℃
, TE6=10
℃
for MSX-07HRN1-QC2, MSX-09HRN1-QC2(2T0032300007
2T0032300007),
MSX-12HRN1-QC2(2T0032500006),
TE5=2
, TE6=
℃
7
℃
for MSX-09HRN1-QC2(2T0032300534),
MSX-12HRN1-QC2(2T0032500185),
MSX-18HRN1-QC2 models;
TE5=2
, TE6=
℃
12
℃
for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models.