6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Connective pipe length
Air purging
Additional amount of
refrigerant
All
Less than 5m
Use vacuum pump
------------------
MSX-07HRN1-QC2
More than 5m
Use vacuum pump
(Pipe length
–
5)
×
20g/m
MSX-09HRN1-QC2
MSX-12HRN1-QC2
MSX-18HRN1-QC2
MSX-21HRN1-QB8W
More than 5m
Use vacuum pump
(Pipe length
–
5)
×
40g/m
MSX-24HRN1-QB8W
Model
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
MSX-07HRN1-QC2
5
8
20
MSX-09HRN1-QC2
MSX-12HRN1-QC2
MSX-18HRN1-QC2
5
10
25
MSX-21HRN1-QB8W
MSX-24HRN1-QB8W