39
cooling mode ,defrosting mode and the current protection.
8.4.3.3 Indoor fan running rules:
When the compressor is off because off the room temperature rising or the protection, the indoor fan
will run at breeze.
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind
function has the priority.
Anti-cold wind function:
When evaporator coil temp.T2 is getting higher,
T2>TE2, the indoor fan will run at setting speed.
TE1<T2<TE2, the indoor fan will run at low speed.
When T2 is getting lower,
TE4<T2<TE3,the indoor fan will run at low speed.
T2<TE4, the indoor fan will shut off.
While TE1=28
,TE2=3
℃
8
,TE3=30
,TE4=2
℃
℃
0
℃
for MSX-07HRN1-QC2, MSX-09HRN1-QC2
models.
TE1=31
,TE2=36
,TE3=30
,TE4=20
℃
℃
℃
℃
for MSX-12HRN1-QC2 model(2T0032500185)
TE1=31
℃
,TE2=36
℃
,TE3=30
℃
,TE4=22
℃
for MSX-12HRN1-QC2 model(2T0032500006)
TE1=34
,TE2=3
℃
7
,TE3=30
,TE4=20
for
℃
℃
℃
MSX-18HRN1-QC2 model.
TE1=25
℃
,TE2=32
℃
,TE3=30
℃
,TE4=20
℃
for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models.
Auto fan action:
Содержание MOA-07HN1-QC2
Страница 1: ...XSEU A 1202 SERVICE MANUAL MIDEA AIRCONDITIONER EUROPE MARKET SPLIT WALL MOUNTED TYPE X ON OFF SERIES...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units MSX 07HRN1 QC2 MSX 09HRN1 QC2 MSX 12HRN1 QC2 MSX 18HRN1 QC2...
Страница 16: ...14 MSX 21HRN1 QB8W MSX 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units MOA 07HN1 QC2...
Страница 18: ...16 MOA1 09HN1 QC2 MOA 09HN1 QC2 MOB1 12HN1 QC2 MOB 12HN1 QC2...
Страница 19: ...17 MOF 18HN1 QC2...
Страница 20: ...18 MOF1 21HN1 QB8W MOF3 24HN1 QB8W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 35: ...33 Ionizer Plasma function indicator This indicator illuminates when Ionizer Plasma function is on...