Parameter
Address
[spacer]
SFMON: Wrong module slot 10
096 109
[spacer]
Module in wrong slot.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Wrong module Dig.Bus
096 123
[spacer]
The device has been fitted with a wrong digital bus. Since this is checked using
the module variant number this signal can also occur after a firmware upgrade
to a version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Wrong module HMI
096 124
[spacer]
The device has been fitted with a wrong HMI. Since this is checked using the
module variant number this signal can also occur after a firmware upgrade to a
version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Wrong module Comm
096 125
[spacer]
The device has been fitted with a wrong communication module. Since this is
checked using the module variant number this signal can also occur after a
firmware upgrade to a version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Wrong module Ana.Bus
096 126
[spacer]
The device has been fitted with a wrong analog bus. Since this is checked using
the module variant number this signal can also occur after a firmware upgrade
to a version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Defect.module slot 1
097 000
[spacer]
SFMON: Defect.module slot 2
097 001
[spacer]
SFMON: Defect.module slot 3
097 002
P631
11 Troubleshooting
11-4
P631/EN M/R-11-C // P631-310-650
Содержание P631
Страница 2: ......
Страница 4: ......
Страница 7: ...Changes after going to press...
Страница 8: ......
Страница 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Страница 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Страница 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Страница 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Страница 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Страница 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Страница 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Страница 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Страница 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Страница 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Страница 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Страница 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Страница 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Страница 637: ......