Parameter
Address
Default
Min
Max
Unit
Logic Diagram
Overload data
acquisition
OL_DA: Overload duration
004 102
Not measured
0.0
6500.0
s
[spacer]
Duration of the overload event.
[spacer]
OL_DA: Status THRM1 replica
004 155
Not measured
0
250
%
[spacer]
Display of the buffer content of the thermal overload protection function THRM1
or THRM2, respectively.
[spacer]
OL_DA: Load current THRM1
004 159
Not measured
0.00
3.00
Inom
[spacer]
Display of the load current used by the thermal overload protection function to
calculate the tripping time.
[spacer]
OL_DA: Object temp. THRM1
004 156
Not measured
-40
300
°C
[spacer]
Display of the temperature of the protected object as determined by function
THRM1 or THRM2, respectively.
[spacer]
OL_DA: Coolant temp.THRM1
004 157
Not measured
-40
215
°C
[spacer]
Display of the coolant temperature of the protected object. Depending on the
setting at THRM1: Select CTA PSx or THRM2: Select CTA PSx for
coolant temperature acquisition, one of the following values will be displayed:
●
Setting
Default temp. value
: Display of the set temperature value.
●
Setting
From PT100
: Display of the temperature measured by the
resistance thermometer.
●
Setting
From 20 mA input
: Display of the temperature measured via the
20 mA input.
[spacer]
OL_DA: Pre-trip t.leftTHRM1
004 158
Not measured
0.0
1000.0
min
[spacer]
Display of the time remaining before the thermal overload protection function
THRM1 or THRM2, respectively, will reach the tripping threshold.
[spacer]
OL_DA: Offset THRM1 replica
004 191
Not measured
-25000
25000
%
[spacer]
Display of the additional reserve if the coolant temperature is taken into
account. This display is relevant if the coolant temperature has been set to a
value below the maximum permissible coolant temperature or, in other words, if
the thermal model has been shifted downwards.
If, on the other hand, the coolant temperature and the maximum permissible
coolant temperature have been set to the same value, then the coolant
temperature is not taken into account and the characteristic is a function of the
current only. The additional reserve amounts to 0 in this case.
P631
8 Information and Control Functions
8-98
P631/EN M/R-11-C // P631-310-650
Содержание P631
Страница 2: ......
Страница 4: ......
Страница 7: ...Changes after going to press...
Страница 8: ......
Страница 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Страница 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Страница 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Страница 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Страница 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Страница 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Страница 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Страница 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Страница 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Страница 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Страница 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Страница 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Страница 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Страница 637: ......