ProCon HT 150 / HT 225
2. Installation
2 I n b etri e b n ahm e
2.1
Choosing installation location
The boiler can be operated dependent or independent of the
room air.
The construction allows the boiler to be installed on any load-
bearing surface.
The boiler room must be dry and frost-free. Do not
contaminate combustion air through homogenous
hydrocarbon (e.g. in solvents, glues, paints
[spray cans]), sulphurous compounds (oil chimney) or through
excessive dust accumulation as this may cause burner
malfunction or corrosion damage.
Due to the low surface temperatures, the gas-condensing boiler
and air/flue gas piping system do not need to be placed at a
distance away from combustible parts.
Use the following minimum clearances for connections and necessary setting and
maintenance works:
•
Mounting the boiler
Mount the boiler in such a way that a heater specialist can connect
the lines at the back of the appliance.
The boiler must be mounted securely and in a horizontal position.
Check it again with a level. If necessary, adjust boiler using
adjustable feet.
The boiler has an integrated siphon:
If any construction work is taking place during the installation of the condensing
boiler that may create heavy formation of dust, the boiler should be protected
against dirt with plastic sheet or the like.
The dimensions specified refers to the basic dimension and do
not include the required minimum clearance of 3% (3cm per meter
of horizontal connection line) from the flue gas system to the
boiler.
2.2
ProCon HT connections
D
A
A A
C
Fig. 2:
Boiler room
Minimum room height: 1800 mm
Dimension
[Dimension in mm]
A 500
B 1000
C 700
D 680
E 1050
Table 1 Mounting dimensions
Fig. 3:
ProCon HT connections
9
Содержание ProCon HT 150
Страница 1: ...1...
Страница 29: ......
Страница 62: ...7 Technical documentation ProCon HT 150 HT 225 7 9 Measurements and connection dimensions Fig 32 62...
Страница 74: ...Notes ProCon HT 150 HT 225 74...
Страница 75: ...HT 150 HT 225 GWB 75 Notes 75...
Страница 76: ...76...