Error code
(Info
level
A0)
Possible cause
140
Invalid LPB...Segment number or unit
number
148
LPB incompatibility...-Interface / basic unit
151
LMU internal error...
152
Error in the LMU...Programming
153
Appliance was locked manually (Reset button)
154
LMU data record in AGU
160
Fan revolution threshold not reached
161
Maximum fan revolution threshold exceeded
162
Error air pressure monitor (will not close)
164
Error heating circuit- flow switch / pressure monitor
180
Chimney sweep function active
181
Control stop function active
183
Appliance is in programming mode
Error code
(Info
level-
ne A0)
Possible cause
Blink
time
Parameters 1 and 2 must be set (even if they
are correct)
0
No error
10
Error outdoor sensor
20
Error Boiler sensor 1
28
Error Flue gas sensor
40
Error Return sensor 1
50
Error Domestic water sensor 1
52
Error Domestic water sensor 2
61
Indoor unit 1 Error
62
Wrong indoor unit 1 connected or wrong radio-
controlled clock connected
77
Error Air pressure sensor
78
Error Hydraulic pressure sensor
81
Short circuit on the LPB... or no bus feed
82
Address mix-up on the LPB...
91
Data loss in EEPROM
92
Hardware error in the electronic system
100
2 Time masters
105
Maintenance request (see page 47)
110
STB actuated
111
Temperature switch actuated
113
Flue gas monitoring unit actuated
117
Hydraulic pressure too high
118
Hydraulic pressure too low
119
Hydraulic pressure switch actuated
130
Flue gas temperature limit exceeded
132
Safety shut-off (e.g. by gas pressure switch)
133
No flame formation at the end of safety time
134
Flame cut off during operation
135
Wrong air supply
ProCon HT 150 / HT 225
6. Troubleshooting
6.1
Error messages
In the case of a permanent LMU error status..., the error display
(16) will be on permanently. In addition to that, the diagnosis code
sent out through flashes on the multifunction display (12). To
clear the error status, press the release button (7) (> 2 s).
6.1.1 Error code
Table 10: