ProCon HT 150 / HT 225
7. Technical documentation
7.5
Display levels
You can only call up the parameters of Groups A, b, C and d. You can also change Group P.
Display ¹)
Display level
LMU... Variable name
Description
15
P
14
General information (End user level) ²)
A 0
Message code
Diagnosis code (system)
3)
A 1
TkIst
Boiler temperature (flow)
A 2
TbwIst1
Domestic water temperature sensor 1
A 3
Pressure
Water or air pressure
A 4
Op. phase
Operation phase of the automatic burner control unit
Temperatures (Specialist level)
b 0
Diagnosis code
LMU... internal DW diagnosis code
3)
b 1
TkRuec
Boiler return temperature
b 2
TbwIst2
Domestic water temperature sensor 2
b 3
TFlue gas
Flue gas temperature
b 4
TiAussen
Outdoor temperature
b 5
TaGem
Mixed outdoor temperature
b 6
TaGed
Rated outdoor temperature
b 7
TvIst
Flow temperature AGU2.500...
Process value (Specialist level)
C 1
Ion. flow
Ionization flow
C 2
Fan rev.
Fan speed
C 3
Fan PWM_AusAkt
Current fan control (PWM)
C 4
RelModLevel
Relative capacity
C 5
Pumpe_PWM
Pump set point value (PWM)
C 6
ek0
Control gap
Set point values (Specialist level)
d 1
Tsoll
Set point value for 2-point or modulation control (PID)
d 2
TkSoll
Current boiler set point value
d 3
Tsindoor
Set point value for indoor temperature
d 4
TbwSoll
Domestic water set point value
d 5
PhzMax
Maximum modulation level in heating operation
d 6
NhzMax
Maximum speed at maximum capacity in heating operation
Parameter (Specialist level) (Prog mode) [Settings for special functions alone or 4)]
P 0
PhzRelMmi
Start-up capacity control stop (only for operating mode without corresponding
set point value potentiometer, otherwise blocked)
P 1
Tr/TvSollMmi
Indoor / Flow set point value (only for operating mode without corresponding
set point value potentiometer, otherwise blocked)
P 2
TbwSollMmi
DW set point value (only for operating mode without corresponding
set point value potentiometer, otherwise blocked)
P 3
Reserved
Reserved
P 4
NqmodMin
Minimum pump speed
P 5
Sth1
Slope Hk1
P 6
DTR1
Parallel shift Hk1
Table 11:
Operation data display
1) Display:
= blink,
= flash
= does not flash
2) You can select Group A parameters by briefly pressing the display mode button
3) The display blinks both ways
4) Setting the heating curve during operation in heating circuit module AGU...
After 8 minutes the display automatically switches to boiler temperature A1