ProCon HT 150 / HT 225
7. Technical documentation
Line
Level
Function
Range
Valu
e
536
Specialist
Max. speed at max. capacity in heating operation (upper speed limit)
0 ... 9950 rpm
7000 rpm
541
Specialist
Maximum modulation level in heating operation
(LmodTL <= PhzMax <= LmodVL)
0 ... 100 %
100%
542
3)
Specialist
Min. boiler capacity in kW
0 ... 32766 kW
15 kW
543
3)
Specialist
Max. boiler capacity in kW
0 ... 32766 kW
75 kW
544
Specialist
Pump - overrun time, max. 210 minutes
(Setting 255: Continuous operation of Q1)
0 ... 255 min
10 min
545
Specialist
Minimum idle time of boiler (heating demand controlled switch hysteresis)
0 ... 3600 s
300 s
551
Specialist
Constants for rapid reduction without ambient effect
0 ... 20
2
552
Specialist
Hydraulic system adjustment
0 ... 255
80
Specialist
Adjustment flags: Message code Sensor interruption suppressed/not suppressed,
0 = Error message suppressed, 1 = Error message
0 ... 255
0 0 1 0 1 1 0 1
B 0
Return sensor
0 / 1
1
B 1
Domestic water sensor
0 / 1
0
B 2
Flue gas sensor
0 / 1
1
B 3
Outdoor sensor
0 / 1
1
B 4
Hydraulic pressure sensor
0 / 1
0
B 5
Flow sensor
0 / 1
1
B 6
Empty
---
0
554
B 7
Empty
---
0
Specialist
Adjustment flags
0 ... 255
0 0 0 1 0 0 0 0
B 0
Empty
0
0
B 1
Domestic water priority, 0 = absolute, 1 = no priority
0 / 1
0
B 2
Function unused
0
0
B 3
Function unused
0
0
B 4
System frost protection, 0 = Off, 1 = On
0 / 1
1
B 5
Function unused
0
0
B 6
Empty
---
0
555
B 7
Empty
---
0
Specialist
Adjustment flags
0 ... 255
0 1 0 0 0 0 0 1
B 0
Must be on 1
0 / 1
1
B 1
Building construction 0 = simple, 1 = complex
0 / 1
1
B 2
Domestic water thermostat
0 / 1
0
B 3
Empty
---
0
B 4
Empty
---
0
558
b 5...7
3-way valve domestic water 010 = On
XXX
010
596
Specialist
Runtime of mixer drive (Time on / Time off)
30 ... 873 s
150 s
605
Specialist
LPB device number of LMU
0 ... 255
2, 3, 4
606
Specialist
LPB segment number of LMU
0 ... 14
0
614
Specialist
Program. input (0: Deerror, 1: Modem funct., 2: Modem funct. neg.logic,
3: Curtain)
0 ... 255
3
615
Specialist
Programmable output K2 (0: Deerror, 1: Message displayed., 2: Alarm signal
3: Operation message, 4: ext. Transf., 5: Q2Y2, 6: DW circ.., 7: Curtain, 8:
Hydr. switch, 9: RegCI, 10: Basic funct.-K2, 11: DW Loading Through
(Durchldg), 12: Analogue threshold)
0 ... 255
0
618
Specialist
Progr. Input on relay clip-in. (0: Deerror, 1: Modem funct., 2: Modem funct.
neg. logic, 3: Curtain, 4: Target set point value spec., 5: Target capacity, 6:
sensor hydr. switch)
0 ... 255
0