ProCon HT 150 / HT 225
4. Hydraulic schemes
•
Component
s
Compo
nent
Typ
e
Code number
Annotation
ProCon HT master
Cascade
96.30000-7082
Included in the scope of delivery:
Outdoor sensor QAC 31, Cascade controller, 2
strap-on sensors QAD 26
ProCon HT slave
Cascade
96.30000-7084
Water deflector
(see Total price list)
Control unit
RVA 63.280/380
94.80100-5510
Wall-mount enclosure for RVA
63
94.85301-5004
Flow sensor for MK
QAD 26
94.19314-5005
94.19314-5002
Length 4 m
Domestic water sensor
QAZ 21
94.19314-5003
Length 6 m
•
Electrical connections
Component
Connection to
Annotation
Outdoor sensor
OS terminal
Two-wire bus
Bus terminal
Bus connection between boiler master and slave as
Well as Wall-mount enclosure
HC flow sensor
Boiler return sensor
Lustre terminal in the
appliance
The strap-on sensors included in the scope of delivery
must be placed on the structure of the water
deflector.
HC pump 1
RVA 63.280
Q2, N,
Flow sensor MK 2
RVA 63.280
B12, M
Pump MK 2
RVA 63.280
Q6,
Mixer motor MK 2
RVA 63.280
Y5, Y6, N,
Domestic water sensor
RVA 63.280
B3, M
Domestic water charge pump
RVA 63.280
Q3, N,
•
Programming:
Change default setting according to specification in the table.
Contro
ller
Line
Set point value
Annotation
RVA 47
17
---
Heating circuit switched off
Module control unit 4
605
5
Device address
Module control unit 5
605
6
Device address
Module control unit 6
605
7
Device address
80
0
No generator
67
00.01
Device address RVA 47
140
1
Device address
141
1
Segment address
RVA 63
148
1
Unadjusted system time
To program the control units RVA 47 and RVA 63 follow the corresponding instruction manuals.
43
Содержание ProCon HT 150
Страница 1: ...1...
Страница 29: ......
Страница 62: ...7 Technical documentation ProCon HT 150 HT 225 7 9 Measurements and connection dimensions Fig 32 62...
Страница 74: ...Notes ProCon HT 150 HT 225 74...
Страница 75: ...HT 150 HT 225 GWB 75 Notes 75...
Страница 76: ...76...