28
Direct tapping of LV
HRC fuses
Using the measuring cable MK 55 (available as a special accessory - see section 3.3)
the test voltage can be directly tapped from LV HRC fuses of size 00 – 3 (6 … 630 A).
Observe the following safety instructions when using the measuring
cable MK 55:
•
The measuring cable MK 55 may only be used by qualified
electricians or persons who have been instructed in electrical
principles.
•
Only safety handles conforming to DIN VDE 0636-201
(EN 60269-2) or DIN VDE 0680-4 (for work performed under live
voltage) may be used for operation.
•
When performing assembly work under live voltage, the work-
specific instructions and documentation of the network operator,
as well as national safety regulations (such as the German TRBS
2131) are to be observed.
•
It is not intended that the fuse in the plug-in adapter of the
measuring cable be replaced by the user.
Connect to an LV HRC fuse as follows:
Step
Description
1
Connect the yellow earthing socket
via the green/yellow earthing lead
to the protective conductor.
2
Connect the black connector of the measuring input U
X
via measuring
cable to the neutral or protective conductor.
3
Connect the MK 55 with the red connector of the measuring input U
X
.
4
Push the plug-in adapter onto the upper contact blade so that it attaches
securely to the fuse attachment.
5
Push the plug-in adapter onto the upper contact blade so that it attaches
securely to the fuse attachment.
CAUTION