37
Step Description
7
If the test voltage is tapped using the HV sensor, guide this now to the line as
described in section 7.2.2.3 to
phase L1
.
8
Start an
offset compensation
with the
button (see page 35).
Result:
The calculated phase correction angle is determined and displayed
below.
9
Stop the measurement with the
Stop
button.
10
Save the measurement profile with the
Save profile
button.
11
Enter a name for the measurement profile and conclude the input with the
OK
button.
Use clear syntax for the name of the measurement profile so that it may
later be identified easily.
If the name of an existing measurement profile is used, the old name will
be overwritten after a prompt to confirm.
0