Technical Manual Presence Detector SCN-P/G360XX.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
20
20
The following table shows the general communication objects:
Number
Name
Length
Usage
0
Light channel 1
–
Output 1
(Day)
1 Bit
Switching function of the light channel for
daytime operation
1
Light channel 1
–
Output 1
(Night)
1 Bit
Switching function of the light channel for
nighttime operation
2
Light channel 1
–
Output 2
1 Bit
Second switching function of the light channel
Table 8: Communication objects - Output object "switching"
Output object: Dimming absolute
If the output object is set to "Dimming absolute", different dimming values for day and night can be
defined:
Figure 11: Settings - Output
o je t Di
i g a solute
In addition, an orientation light can be activated to leave the room. The orientation light is called up
when the follow-up time of the light channel has expired. Without orientation light, the channel
would be switched off without delay. The orientation light now causes the output to call up the
parameterised value for the switch-off delay day/night. The light channel is not switched off until the
switch-off delay for day/night has expired.
I additio to the output o je t Di
i g a solute , a se o d output o je t "S it hi g" is displa ed.
The following table shows the general communication objects:
Number
Name
Length
Usage
0
Light channel 1
–
Output 1
–
Dimming absolute
1 Byte
Dimming function of the light channel
2
Light channel 1
–
Output 2 -
Switching
1 Bit
Second switching function of the light channel
Table 9: Communication objects - Output object "Dimming absolute"