Technical Manual Presence Detector SCN-P/G360XX.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
15
15
4.2 Light Channel 1/2/3/4/HCV
Up to 4 lighting groups can be activated for all presence detectors with 4 sensors and up to 3 lighting
groups for all detectors with 3 sensors. In addition, a HCV channel and an alarm channel
(see 4.3 Alarm) can be activated.
4.2.1 General Settings
The following figure shows the basic settings for a light channel:
Figure 7: Basic settings - light channel
The following table shows the possible settings for these parameters:
ETS-Text
Dynamic range
[Default value]
Comment
Active sensors
1-4
1234
Setting which sensors are active for the
selected channel
Sensitivity
Basic setting (General
setting)
individual
Basic setting:
The sensitivity values set
in the General Settings menu are used.
Individual
: Individual sensitivity values
can be set for this light channel.
Brightness
(only light channels)
Basic setting (General
setting)
Basic setting or active
o je t Dark
Independent of
brightness
Basic setting:
The light channel uses
the brightness settings of the general
settings.
Basi setti g or a tive o je t Dark :
The light channel uses the brightness
settings of the general settings, but can
be switched independent of brightness
with a "1" to the object "Dark".
Independent of brightness:
The light
channel switches independently of the
measured brightness