Technical Manual Presence Detector SCN-P/G360XX.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
16
16
Motion filter in
standby
not active, no filtering
active, filter short
movement
Only in fully automatic mode!
Activation of a motion filter in standby
mode (= output is switched off)
Number of monitoring
time slots
(only for HCV)
0-30
[3]
Definition of how many movements
have to be detected before switch-on
Length of monitoring
time slot
(only for HCV)
0-30000s
[30s]
Determination of the length for a
monitoring time slot
Table 4: Basic settings - light channel
The para eters „ right ess a d „ o itori g ti e slots are e plai ed i ore detail elo
:
Brightness (only light channels)
Sensor activation/deactivation is only available for the light group. In this way, the presence
detector can be assigned a specific work area. The parameter "Sensor activation below" defines
the brightness threshold below which the detector detects presence. No movement is detected
above this threshold, but the detector does not switch off the light as soon as the brightness is
exceeded. This can be achieved with the parameter "Switch-off when exceeding". However, this
value should not be set too low, as this can result in a continuous on/off switching.
Monitoring time slot (only HCV)
The monitoring time slot is only available for one HCV channel. This means that a longer
detection time is required for switching on. In order to switch on the channel, at least, one
detection must have taken place in each of the set monitoring time slots
4.2.2 Channel Mode Selection
A distinction can be made between two operating modes: Fully automatic and half-automatic:
Fully automatic
If the motion detector is set as fully automatic, each detected presence causes the output to
be switched on and is switched off again after the follow-up time has expired.
Half automatic
In half automatic mode, the output is switched on via the "External push-button short"
object and is automatically switched off again after the follow-up time has expired..